Plan Review Notes
Plan Review Notes For Permit 21061851
Permit Number 21061851
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-26 13:55:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO INDICATIONS THAT THE BUILDINGS WILL
 REMIAN OCCUPIED, OR NOT OCCUPIED, DURING THE ANY PART
 OR ENTIRE CONSTUCTION PROCESS.
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN AND INCLUDE
 AN APPLICABLE NOTE AS TO THE INTENT TO OCCUPY OR VACATE
 UNTIL ALL FINAL INSPECTIONS.
  
 SHOULD THE INTENT BE TO OCCUPY THE LIFE SAFETY PLAN
 SHALL INCLUDE SPECIFIC DETAILS TO PROTECT THE OCCUPANTS
 AND THAT ALL EXITS SHALL ARE FUNCTIONAL OR ALTENATE
 EXITS ARE PROVIDE WITHIN THE REQUIRMENTS OF THE LIFE
 SAFETY CODE.
  
 PER NFPA 241
  
 CHAPTER 1 ADMINISTRATION
  
 1.1* SCOPE. THIS STANDARD SHALL APPLY TO STRUCTURES IN
 THE
 COURSE OF CONSTRUCTION, ALTERATION, OR DEMOLITION,
 INCLUDING
 THOSE IN UNDERGROUND LOCATIONS.
 1.2 PURPOSE. THIS STANDARD IS INTENDED TO PRESCRIBE
 MINIMUM
 SAFEGUARDS FOR CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS
 IN ORDER TO PROVIDE REASONABLE SAFETY TO LIFE AND
 PROPERTY
 FROM FIRE DURING SUCH OPERATIONS.
 1.3 APPLICATION.
 1.3.1* THIS STANDARD PROVIDES MEASURES FOR PREVENTING
 OR
 MINIMIZING FIRE DAMAGE DURING CONSTRUCTION, ALTERATION,
 AND
 DEMOLITION OPERATIONS.
  
 CHAPTER 7 FIRE PROTECTION
  
 7.1 FIRE SAFETY PROGRAM.
 7.1.1 AN OVERALL CONSTRUCTION OR DEMOLITION FIRE SAFETY
 PROGRAM
 SHALL BE DEVELOPED.
 7.1.2 ALL OF THE FOLLOWING ITEMS SHALL BE ADDRESSED IN
 THE FIRE
 SAFETY PROGRAM:
 (1) GOOD HOUSEKEEPING
 (2) ON-SITE SECURITY
 (3) FIRE PROTECTION SYSTEMS
 (A) FOR CONSTRUCTION OPERATIONS, INSTALLATION OF NEW
 FIRE
 PROTECTION SYSTEMS AS CONSTRUCTION PROGRESSES
 (B) FOR DEMOLITION OPERATIONS, PRESERVATION OF EXISTING
 FIRE PROTECTION SYSTEMS DURING DEMOLITION
 (4) ORGANIZATION AND TRAINING OF AN ON-SITE FIRE
 BRIGADE
 (5) DEVELOPMENT OF A PREFIRE PLAN WITH THE LOCAL FIRE
 DEPARTMENT
 (6) RAPID COMMUNICATION
 (7) CONSIDERATION OF SPECIAL HAZARDS RESULTING FROM
 PREVIOUS
 OCCUPANCIES
 (8) PROTECTION OF EXISTING STRUCTURES AND EQUIPMENT
 FROM EXPOSURE
 FIRES RESULTING FROM CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS
 7.2 OWNER?S RESPONSIBILITY FOR FIRE PROTECTION.
 7.2.1* THE OWNER SHALL DESIGNATE A PERSON WHO SHALL BE
 RESPONSIBLE
 FOR THE FIRE PREVENTION PROGRAM AND WHO SHALL ENSURE
 THAT IT IS CARRIED OUT TO COMPLETION.
  
 8.2* SCAFFOLDING, SHORING, AND FORMS.
 8.2.1 ACCUMULATIONS OF UNNECESSARY COMBUSTIBLE FORMS OR
 FORM LUMBER SHALL BE PROHIBITED.
 8.2.2 COMBUSTIBLE FORMS OR FORM LUMBER SHALL BE BROUGHT
 INTO THE STRUCTURE ONLY WHEN NEEDED.
 8.2.3 COMBUSTIBLE FORMS OR FORM LUMBER SHALL BE REMOVED
 FROM THE STRUCTURE AS SOON AS STRIPPING IS COMPLETE.
 8.2.4 THOSE PORTIONS OF THE STRUCTURE WHERE COMBUSTIBLE
 FORMS ARE PRESENT SHALL NOT BE USED FOR THE STORAGE OF
 OTHER
 COMBUSTIBLE BUILDING MATERIALS.
  
 CHAPTER 10 SAFEGUARDING DEMOLITION OPERATIONS
 10.1 GENERAL. IN ADDITION TO THE SPECIFIC REQUIREMENTS
 OF THIS
 CHAPTER, THE PROVISIONS OF CHAPTER 1 AND CHAPTERS 3
 THROUGH 7
 SHALL BE FOLLOWED, AS APPLICABLE, FOR ALL DEMOLITION
 OPERATIONS.
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AS
 APPLICABLE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL