Plan Review Notes For Permit 21061840 |
Permit Number |
21061840 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-01-27 11:23:58 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21061840 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE 2 KITCHEN CALCULATIONS ARE CONFUSING AS THEY | | HAVE DIFFERENT SQUARE FOOTAGE. IT APPEARS THAT THE TOP | | KITCHEN CALCULATION IS FOR THE OUTDOOR AIR AND THE | | LOWER CALCULATION IS FOR THE REQUIRED EXHAUST | | CALCULATION. PLEASE MAKE SURE THAT THE SQUARE FOOTAGE | | IS THE SAME FOR BOTH CALCULATIONS. IT ALSO APPEARS THAT | | THE OUT DOOR AIR TABLE IS TITLED 2020 FLMC VENTILATION | | CALCULATIONS BUT IT APPEARS THAT THE CALCULATIONS HAVE | | ASHRAE REFERENCE NUMBERS. PLEASE REMOVE ALL REFERENCE | | TO ASHRAE AS THE TITLE REFLECTS THE USE OF THE 2020 | | FLORIDA MECHANICAL CODE. YOU CAN NOT MIX AND MATCH. FBC | | M403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|