Plan Review Notes
Plan Review Notes For Permit 21061840
Permit Number 21061840
Review Stop M
Sequence Number 3
Notes
Date Text
2022-01-27 11:23:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061840
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE 2 KITCHEN CALCULATIONS ARE CONFUSING AS THEY
 HAVE DIFFERENT SQUARE FOOTAGE. IT APPEARS THAT THE TOP
 KITCHEN CALCULATION IS FOR THE OUTDOOR AIR AND THE
 LOWER CALCULATION IS FOR THE REQUIRED EXHAUST
 CALCULATION. PLEASE MAKE SURE THAT THE SQUARE FOOTAGE
 IS THE SAME FOR BOTH CALCULATIONS. IT ALSO APPEARS THAT
 THE OUT DOOR AIR TABLE IS TITLED 2020 FLMC VENTILATION
 CALCULATIONS BUT IT APPEARS THAT THE CALCULATIONS HAVE
 ASHRAE REFERENCE NUMBERS. PLEASE REMOVE ALL REFERENCE
 TO ASHRAE AS THE TITLE REFLECTS THE USE OF THE 2020
 FLORIDA MECHANICAL CODE. YOU CAN NOT MIX AND MATCH. FBC
 M403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  