Plan Review Notes
Plan Review Notes For Permit 21061840
Permit Number 21061840
Review Stop P
Sequence Number 1
Notes
Date Text
2021-08-18 10:03:511) SHTS. A1.0 & A8.1 - THE DOOR IN THE WOMEN'S AND
 MEN'S RESTROOMS APPEAR TO BE SWINGING INTO THE CLEAR
 FLOOR SPACE FOR THE LAVATORY.COMPLY WITH FBC-ACCESS.
 SEC.603.2.3 EXCEPTION #2. SHOW THE CLEAR FLOOR SPACE
 BEYOND THE ARC OF THE DOOR SWING COMPLYING WITH
 FBC-ACCESS. SEC.305.3.
 2) SHT.A3.0 - PROVIDE COMPLETE SCUPPER DIMENSIONS ON
 THE PLANS.COMPLY WITH FBC-PLUMBING SEC.1108.3.
 3) SHT. A8.1 - DETAIL "A" - ACCESSIBLE NOTE "A"
 REFERENCES THE ADA. THE STATE OF FLORIDA DOES NOT
 ENFORCE THE ADA. THE STATE OF FLORIDA ENFORCES THE
 FBC-ACCESSIBILITY WHICH IS A DEPT. OF JUSTICE COMPLIANT
 CODE. REMOVE ALL NOTES REFERRING TO ADA.
 4) SHT. A8.1 - DETAILS #1, 2, 5, 6 SHOW A VERTICAL GRAB
 BAR. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER FBC- ACESS. SEC.609.4.THERE IS NO
 EXCEPTION FOR VERTICAL GRAB BARS, EVEN IF THEY ARE NOT
 REQUIRED.REMOVE THE VERTICAL GRAB BARS.ALSO, SEE SHT.
 ADA 1.0.
 5) SHT. A8.1 - DETAIL # A - THERE IS A NOTE THAT REFERS
 TO ANSI A117.1. THIS STANDARD IS NOT APPLICABLE. THE
 STANDARD IS FBC-ACCESS.
 6) SHT. P1.0 - DETAIL #H - THE BACKFLOW DEVICES LISTED
 ARE FOR CARBONATED BEVERAGE MACHINES ONLY. BACKFLOW
 PREVENTERS FOR THE WATER FILTERS, REVERSE OSMOSIS
 SYSTEM AND NON-CARBONATED BEVERAGE MACHINES SHALL
 COMPLY WITH FBC-PLUMBING TABLE 608.1 AND ASSE 1024.
 7) THE MAXIMUM SIZE OF ANY SINGLE TANK FOR A GREASE
 INTERCEPTOR SHALL BE 1250 GALLONS PER CITY STANDARD
 DRAWING GS-7.
 8) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE MOP
 SINK DUE TO THE ECOLAB SYSTEM PER FBC-PLUMBING SEC.
 608.7 AND TABLE 608.1.
 9) TEMPERED OR COLD WATER IS REQUIRED AT THE LAVATORIES
 IN THE TOILET ROOMS PER FBC-PLUMBING SEC.419.5.
 10) CLEAR WATER WASTE SHALL NOT BE DISCHARGED TO THE
 GREASE WASTE SYSTEM PER FBC-PLUMBING SEC.1003.2.
 11) SUBMIT DETAILS OF THE GREASE INTERCEPTOR. THE
 INTERCEPTOR SHALL CCOMPLY WITH CITY STANDARD DRAWING
 GS-7 OR GS 7.1. PLEASE CONTACT THE CITY OF WEST PALM
 BEACH ENGINEERING DEPT. AT 561-494-1079 OR 561-835-7423
 FOR A COPY OF THE STANDARD DRAWING.
 12) THE SIZING OF THE GREASE INTERCEPTOR SHALL COMPLY
 WITH FBC-PLUMBING SEC.1003.3.5. THE INTERCEPTOR SHALL
 BE SIZED BASED ON PDI G101 OR RULE 64E-6, FLORIDA
 ADMINISTRATIVE CODE.
 13) SUBMIT A SITE PLAN OR CIVIL PLAN SHOWING THE
 LOCATION OF THE GREASE INTERCEPTOR ON THE PARCEL. WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 14) A HOT WATER RECIRCULATION LINE IS REQUIRED PER
 FBC-PLUMBBING SEC.607.2.THE RECIRCCULATION SSYTEM SHALL
 COMPLY WITH FBC-ENERGY SEC.C404.6, C404.6.1
 15) A FULL OPEN VALVE IS REQUIRED AT THE TOP OF THE
 DOWNFEED WATER PIPE FROM THE ROOF TO THE STRUCTURE PER
 FBC-PLUMBING SEC.606.1 (5).
 16) SHT. P3.0 - A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW PREVENTION DEVICE AT THE WATER METER. THIS
 DEVICE SHALL BE A REDUCED PRESSURE ZONE VALVE BACKFLOW
 PREVENTER. PLACE A NOTE ON THE PLANS STATING A SEPARATE
 PERMIT IS REQUIRED AND THE DEVICE IS AN RPZ BACKFLOW.
 17) SHT P3.0 - THERE IS A NOTE AT THE BACKFLOW DEVICE
 STATING "FOR CONTINUATION, SEE CIVIL DRAWINGS." THERE
 ARE NO CIVIL DRAWINGS SHOWING THIS INFORMATION.
 CLARIFY.
 18) THE SIZING OF THE HEATED WATER SUPPLY PIPING SHALL
 BE IN ACCORDANCE WITH FBC- ENERGY SEC. C404.5.1 OR
 C404.5.2. SHOW COMPLIANCE ON THE WATER RISER.
 19) SINCE THE OCCUPANT LOAD OF THIS SPACE IS LESS THAN
 50 PERSONS IT SHALL BE CLASSIFIED AS A "B" OCCUPANCY IN
 ACORDANCE WITH FBC-BUILDING SEC.303.1.1 AND HENCE, 2
 RINKING FOUNTAINS ARE REQUIRED PER FBC-ACCESS.
 SEC.211.2 AND FBC-PLUMBING SEC.410..3.
 20) HAND SINKS SHALL NOT DISCHARGE TO THE GREASE WASTE
 SYSTEM PER FBC-PLUMBING SEC.1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  