2021-08-20 09:42:13 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21061840 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE ADD A NOTE ON THE PLANS STATING THAT THE HOOD |
| SYSTEM WILL REQUIRE A SEPARATE PERMIT APPLICATION, |
| DRAWINGS AND REVIEW. THE HOOD SYSTEM WILL NOT BE |
| REVIEWED UNDER THIS PERMIT. |
| |
| 2) PLEASE ADD A NOTE ON THE PLANS STATING THAT THE |
| REFRIGERATION SYSTEMS WILL REQUIRE A SEPARATE PERMIT |
| APPLICATION, DRAWINGS AND REVIEW. THE REFRIGERATION |
| SYSTEMS WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| |
| 3) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC |
| C402.1 |
| |
| 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. FBC EC C403.2.1 |
| |
| 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS PER FBC |
| 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 6) PLEASE SHOW THE CLEARANCE TO THE ROOF EDGE OR THE |
| GUARDS. FBC M 304.11 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |