Plan Review Notes
Plan Review Notes For Permit 21061840
Permit Number 21061840
Review Stop G
Sequence Number 1
Notes
Date Text
2021-08-19 14:34:051) SUBMIT COPIES OF THE MANUFACTURER'S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC- FUEL GAS CODE SEC. 402.2, AND 301.3.GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FBC-FUEL GAS CODE SEC.305.1.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-FUEL GAS CODE SEC.304.1. WHERE COMBUSTION AIR IS
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR. FBC-FUEL GAS SEC.304.9.3 OR FBCR
 G2407.9.3.
 3) SUBMIT COPIES OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE FBC-FUEL GAS
 SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) THRU
 402.4 (37).
 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED & ALL
 PIPE SIZES ON THE GAS RISER .WPB AMEND. TO FBC SEC.
 107.2.1.
 5) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. NFPA
 96-14. SECS. 10.4.1, 10.4.3, 10.4.4, 10.5.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  