Plan Review Notes For Permit 21061694 |
Permit Number |
21061694 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-07-19 10:08:40 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21061694 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET FP 1 OF 1: UNDERGROUND SYMBOLS LEGEND IS | | INDICATING AN EXISTING 4 INCH BACKFLOW PREVENTER BUT | | THE DRAWING SHOWS THE SAME SYMBOL AS A NEW 4 INCH DDCV. | | FBC 107.2.1 | | | | 2) IN THE MATERIALS & ABBREVIATIONS CHART IT SHOWS A | | 6-INCH UNDERGROUND D.I.P. BUT THE DRAWING SHOWS IT TO | | BE A 4-INCH. PLEASE MAKE THE DRAWINGS CONSISTENT. FBC | | 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|