 THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT, WITH THE FOLLOWING COMMENTS:
  
  
 HYDROSTATIC TESTS. ALL PIPING AND ATTACHED
 APPURTENANCES SUBJECTED TO SYSTEM WORKING PRESSURE
 SHALL BE HYDROSTATICALLY TESTED AT 200 PSI (13.8 BAR)
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR 2
 HOURS.
  
 DO NOT COVER/BURY FIRE LINE PIPING OR PAINT BOLTS PRIOR
 TO INSPECTIONS.
  