2021-07-20 18:08:231ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21061640
 7/20/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P201 & P401: EFD-1 BY JSK-1 IS LABELED AS HCWC-1 ON
 THE RISER DRAWING- SECTION 107.2.1 WPB.
  
 2) P201 & P401: THE WATER CLOSETS (WC-1) AND (HCWC-1)
 NO NOT APPEAR TO BE VENTED. PLEASE INDICATE WHICH
 METHOD OF VENTING IS BEING UTILIZED FOR THE FIXTURES-
 SEE SECTIONS- 910, 911, 912 FBC P.
  
 3) P401: THE STORM DRAIN ISOMETRIC (DETAIL 1) IS
 MISLABELED AS SANITARY ISOMETRIC PLAN- SECTION 107.2.1
 WPB.
  
 4) P301 & P401: PROVIDE WATER HAMMER ARRESTORS FOR
 SUPPLY LINES TO THE FLUSH VALVES- SECTION 604.9 FBC P.
  
 5) P501: THE THERMAL EXPANSION TANK SHALL BE INSTALLED
 ON THE COLD WATER LINE DOWNSTREAM OF THE CHECK VALVE-
 SECTION 607.3 FBC P.
  
 6) P501: THE DIMENSIONS IN THE DRINKING FOUNTAIN
 (DETAIL 6) ARE NOT LEGIBLE- SECTION 107.2.1 WPB.
  
 7) P501: PROVIDE THE EFFICIENCY RATING OF THE EWH IN
 THE SCHEDULE- TABLE C404.1 FBC EC.
  
 8) P101 & P201: PLEASE PROVIDE NOTES ON THE PLAN TO
 CLARIFY THE SCOPE OF THE STORM DRAIN WORK. THE 7TH
 FLOOR DECK DOES NOT APPEAR TO BE AN APPROVED PLACE OF
 DISPOSAL FOR THE DRAINS- SECTION 1001.2 FBC P. IS THIS
 A NEW SPILL LOCATION FOR THE DRAINS?
  
 9) P501: THE PLUMBING FIXTURE RIM HEIGHTS WERE NOT
 PLACED IN THE COLUMN IN THE PLUMBING FIXTURE SCHEDULE-
 SECTION 404.1 FBC P.
  
 10) A4.10 & A5.10- MISSING ACCESSIBLE FIXTURE DETAILS
 PER FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAGRAMS AND DIMENSIONS- SECTION
 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 11) A5.10: THE HEIGHT OF THE LAVATORY SINK RIM OR
 COUNTER SURFACE (DETAIL 8) SHALL BE 34 INCHES FROM THE
 FINISHED FLOOR- SECTIONS 213.3.4 AND 606.2 FBC ACC.
  
 12) A5.10 DETAIL 8: PROVIDE COMPLETE KNEE AND TOE
 CLEARANCE DIMENSIONS PER FIGURES- 306.2 & 306.3 FBC
 ACC.
  
 13) A4.10: REFER TO SECTIONS 213.3.3 AND 605 FBC ACC
 AND CLARIFY IF AN ACCESSIBLE URINAL IS TO BE INSTALLED,
 AND PROVIDE THE MISSING ACCESSIBLE FIXTURE DETAILS.
  
 14) A4.10: PROVIDE THE STANDARD WATER CLOSET CENTERLINE
 MEASUREMENTS FROM THE PARTITIONS- SECTION 405.3.1 FBC
 P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  