Plan Review Notes
Plan Review Notes For Permit 21061620
Permit Number 21061620
Review Stop NFIP
Sequence Number 2
Notes
Date Text
2021-07-08 10:23:04PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD
 ELEVATION SHALL BE NOT LESS THAN 9.0 FEET NAVD.
  
 1. SECTION A6 CORRECTED
  
 2. SECTION A9A)
 GARAGE SF IS INDICATED AS 572 SF. PLAN PAGE SP-1.01
 STATES GARAGE SF IS 597 SF. PLEASE CORRECT.
  
 NEW COMMENT:
 REVISED PLAN PAGE SP-1.01 SUBMITTED FOR REVIEW. SUBMIT
 CHANGES TO APPROVED PLANS AS A REVISION TO MASTER
 PERMIT 19050988.
 NOTICE: FEMA REQUIRES THE SQUARE FOOTAGE OF THE GARAGE
 TO BE MEASURED ON THE OUTSIDE OF THE GARAGE. PLEASE
 RE-EVALUATE THE SQUARE FOOTAGE. SEE COMMENTS UNDER
 BLDG. REVIEW.
  
 3. SECTION A9B) CORRECTED
  
 4. SECTION B8
 FLOOD ZONE SHOULD ONLY BE AE. (REMOVE THE REFERENCE TO
 ZONE X. ZONE X IS NOT A SPECIAL FLOOD HAZARD AREA)
  
 5. SECTION B9
 BASE FLOOD ELEVATIONS SHOULD BE 6.0 FEET AND 7.0 FEET
 NAVD. (REMOVE THE REFERENCE TO 0.2% ANNUAL CHANCE OF
 FLOOD. THIS PERTAINS TO ZONE X-500 WHICH IS NOT A
 SPECIAL FLOOD HAZARD AREA)
  
 6. SECTION D
 INCLUDE THE FUTURE GENERATOR SHOWN ON PLAN PAGE SP-1.01
 IN THE COMMENTS SECTION UNDER EQUIPMENT SERVICING THE
 BUILDING.
 (COMMENT FOR THE GENERATOR STATES "GENERATOR SLAB IS AT
 ELEVATION 9.6 NAVD AND BOTTOM OF THE GENERATOR IS AT
 ELEVATION 10.3 NAVD". PLEASE CLARIFY.
  
 NEW COMMENT:
  
 7. PROVIDE A FINAL BOUNDRY LINE SURVEY PER FEMA EC
 INSTRUCTIONS ITEM C2.
  
 NOTICE: SUBMITTAL FOR FINISHED CONSTRUCTION EC SHOULD
 INCLUDE ONLY THE EC AND A FINAL BOUNDRY LINE SURVEY.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  