2021-06-28 14:55:20PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD
 ELEVATION SHALL BE NOT LESS THAN 9.0 FEET NAVD.
  
 1. SECTION A6
 PHOTOGRAPHS MUST SHOW THE FOUNDATION WITH
 REPRESENTATIVE EXAMPLES OF THE FLOOD OPENINGS OR VENTS.
  
 2. SECTION A9A)
 GARAGE SF IS INDICATED AS 572 SF. PLAN PAGE SP-1.01
 STATES GARAGE SF IS 597 SF. PLEASE CORRECT.
  
 3. SECTION A9B)
 NUMBER OF VENTS IS INDICATED AS 2. PLAN PAGE A1.01
 STATES THERE SHALL BE 3 VENTS INSTALLED.
 REF. ICC-ES REPORT FOR THE FOLLOWING:
 SMART VENT MODEL 1540-520 (8 X 16) ONLY COVERS 200 SF
 EACH. 3 VENTS ARE REQUIRED PER APPROVED PLAN.
  
 4. SECTION B8
 FLOOD ZONE SHOULD ONLY BE AE.
  
 5. SECTION B9
 BASE FLOOD ELEVATIONS SHOULD BE 6.0 FEET AND 7.0 FEET
 NAVD
  
 6. SECTION D
 INCLUDE THE FUTURE GENERATOR SHOWN ON PLAN PAGE SP-1.01
 IN THE COMMENTS SECTION UNDER EQUIPMENT SERVICING THE
 BUILDING.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.