2021-06-28 14:55:20 | PLAN REVIEW / NFIP |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| CITY ORDINANCE NO. 4658-16 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: |
| |
| PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD |
| ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD |
| ELEVATION SHALL BE NOT LESS THAN 9.0 FEET NAVD. |
| |
| 1. SECTION A6 |
| PHOTOGRAPHS MUST SHOW THE FOUNDATION WITH |
| REPRESENTATIVE EXAMPLES OF THE FLOOD OPENINGS OR VENTS. |
| |
| 2. SECTION A9A) |
| GARAGE SF IS INDICATED AS 572 SF. PLAN PAGE SP-1.01 |
| STATES GARAGE SF IS 597 SF. PLEASE CORRECT. |
| |
| 3. SECTION A9B) |
| NUMBER OF VENTS IS INDICATED AS 2. PLAN PAGE A1.01 |
| STATES THERE SHALL BE 3 VENTS INSTALLED. |
| REF. ICC-ES REPORT FOR THE FOLLOWING: |
| SMART VENT MODEL 1540-520 (8 X 16) ONLY COVERS 200 SF |
| EACH. 3 VENTS ARE REQUIRED PER APPROVED PLAN. |
| |
| 4. SECTION B8 |
| FLOOD ZONE SHOULD ONLY BE AE. |
| |
| 5. SECTION B9 |
| BASE FLOOD ELEVATIONS SHOULD BE 6.0 FEET AND 7.0 FEET |
| NAVD |
| |
| 6. SECTION D |
| INCLUDE THE FUTURE GENERATOR SHOWN ON PLAN PAGE SP-1.01 |
| IN THE COMMENTS SECTION UNDER EQUIPMENT SERVICING THE |
| BUILDING. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |