| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 4TH REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: UPON PEER RIVEW OF THE ELEVATION CERTIFICATE, A |
| CODE REQUIREMENT WAS MISSED ON THE LAST BLDG REVIEW. |
| SEE BELOW: |
| |
| 1.STATEMENT BY DESIGNER ON PLANS REQUIRED. |
| FBC R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD |
| ELEVATION. |
| 2.1.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS SHALL |
| BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH |
| SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE |
| ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE |
| ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS |
| ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS |
| SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN |
| PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL |
| PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON |
| EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND |
| EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF |
| ASCE 24. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |