2021-07-08 08:16:59 | 07/08/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE SUPPLY A LICENSED PLUMBING CONTRACTOR FOR THE |
| SCOPE OF WORK, UNDER CONSTRUCTION INDUSTRY LICENSING |
| BOARD OF PALM BEACH COUNTY STANDARDS FOR CERTIFIED |
| CATEGORIES PER CHAPTER 67-1876, SPECIAL ACT, LAWS OF |
| FLORIDA, AS AMENDED (REV. 10/30/17) DOES NOT ALLOW YOUR |
| LICENSE TO INSTALL A BACKFLOW (CGC). |
| |
| 2. PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS FOR |
| THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF |
| THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE |
| WORK SECTION ON THE PERMIT APPLICATION. |
| |
| 3. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE |
| WHICH CONTAINS NOT MORE THAN 0.25% PERCENT LEAD. |
| |
| 4. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS |
| ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY |
| OF SOUTHERN CALIFORNIA (USC). YOU MAY CONTACT THE |
| DEPARTMENT OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT |
| 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE |
| PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY |
| REQUIREMENTS. |
| |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |