Plan Review Notes
Plan Review Notes For Permit 21061357
Permit Number 21061357
Review Stop B
Sequence Number 3
Notes
Date Text
2021-07-16 13:45:43JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL2533-R25 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R25 SELECTED SYSTEM NO. W-4 DO NOT MEET
 THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN PRESSURE
 REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND
 SEALED ENGINEERED NAILING CALCULATION FOR ZONE 3. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
  