Date |
Text |
2021-08-11 08:13:57 | REVISION - BUILDOUT |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| 1) PLEASE SHOW RESTROOM FLOOR AND BASE BOARD TO COMPLY |
| WITH FBC 1210.2.1FLOORS AND WALL BASES. |
| IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND |
| SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH |
| FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE |
| WALLS NOT LESS THAN 4 INCHES (102 MM). (DRYWALL IS NOT |
| CONSIDERED A HARD SURFACE FOR THE BASE BOARD) |
| 2) PLEASE SHOW RESTROOM AND MOP SINK AREA WALL FINISH |
| TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE). |
| 3) (NO CHANGES) PLEASE SHOW ACCESSIBLE RESTROOM MIRRORS |
| MAXIMUM HEIGHT FROM THE FINISHED FLOOR TO THE BOTTOM OF |
| THE "REFLECTIVE SURFACE" FBC (A) 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| 4) NEW DRAWINGS NEED TO BE IN THE "DRAWINGS" FOLDER IN |
| PROJECTDOX. DRAWINGS IN THE "SIGNATURE" FOLDER IN |
| PROJECTDOX CANNOT BE MARKED APPROVED. IF NEEDED ADD TO |
| BOTH "SIGNATURES" AND "DRAWINGS" FOLDER. |
| |