2021-08-11 08:13:57REVISION - BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW RESTROOM FLOOR AND BASE BOARD TO COMPLY
 WITH FBC 1210.2.1FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM). (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE FOR THE BASE BOARD)
 2) PLEASE SHOW RESTROOM AND MOP SINK AREA WALL FINISH
 TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE).
 3) (NO CHANGES) PLEASE SHOW ACCESSIBLE RESTROOM MIRRORS
 MAXIMUM HEIGHT FROM THE FINISHED FLOOR TO THE BOTTOM OF
 THE "REFLECTIVE SURFACE" FBC (A) 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 4) NEW DRAWINGS NEED TO BE IN THE "DRAWINGS" FOLDER IN
 PROJECTDOX. DRAWINGS IN THE "SIGNATURE" FOLDER IN
 PROJECTDOX CANNOT BE MARKED APPROVED. IF NEEDED ADD TO
 BOTH "SIGNATURES" AND "DRAWINGS" FOLDER.
  