2021-07-23 10:38:031) THE FLOORS AND WALL BASES OF THE TOILET ROOMS SHALL
 COMPLY WITH FBC-BUILDING SEC. 1210.2.1.SHOW THE WALL
 FINISH ON THE PLANS. EPOXY PAINT ON DRYWALL DOES NOT
 COMPLY WITH THE CODE.
 2) SHOW THE RESTROOM AND MOP SINK WALL FINISH ON THE
 PLANS. THE WALL FINISH SHALL COMPLY WITH FBC-PLUMBING
 SEC.1210.2.2. EPOXY PAINT ON DRYWALL DOES NOT COMPLY
 WITH THE CODE.
 3) THE MIRROR IN THE TOILET ROOM SHALL BE MEASURED A
 MAXIMUMOF 40 INCHES FROM THE FINISH FLOOR TO THE BOTTOM
 OF THE REFLECTIVE SURFACE PER FBC-ACCESS. SEC.603.3.
 4) SHT. A2.0 - DETAIL #8 - RECESSED SOAP DISPENSER -
 THE OPERABLE PARTS SHALL BE WITHIN THE REACH RANGES PER
 SEC. 308 OF FBC-ACCESS. SHOW THE HEIGHT ON THE DETAIL.
 5) SHT. A2.0 - DETAIL #6 - THE OPERABLE PARTS OF THE
 HCPT SHALL BE WITHIN THE REACH RANGES PER SEC. 308 OF
 FBC-ACCESS. SHOW THE HEIGHT ON THE DETAIL.
 6) SHT. A2.0 - THE TOILET PAPER DISPENSER SHALL COMPLY
 WITH FBC-ACCESS. SEC. 309.4 AND SHALL BE 7 INCHES
 MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER (
 NOT TO THE CENTER OF THE FIRST DISPENSER.)
 7) SHT. A2.0 - DETAIL #1 - THE GRAB BAR BEHIND THE
 WATER CLOSET IS SHOWN AS BEING MEASURED TO THE
 CENTERLINE OF THE GRAB BAR FROM THE FINISH FLOOR AND
 ALSO TO THE TOP OF THE BAR. THE GRAB BAR SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER
 FBC-ACCESS SEC. 609.4.
 8) SHT. A2.0 - DETAIL #1 - THE GRAB BAR BEHIND THE
 WATER CLOSET SHALL BE LOCATED PER FBC-ACCESS. SEC.
 604.5.2 & FIGURE 604.5.2.SHOW THE DIMENSIONS ON THE
 DETAIL.
 9) SHT. A2.0 - THE PLANS REFERENCE DETAILS #1 & #2 ON
 SHT. A2.1. THERE IS NO SHT. A2.1 IN THIS SUBMITTAL.
 CLARIFY.
 10) SHOW THE INSIDE CLEAR DIMENSIONS OF THE TOILET
 ROOMS AND ALSO OF THE CLEAR FLOOR SPACES FOR THE WATER
 CLOSETS AND LAVATORIES.COMPLY WITH FBC-ACCESS.
 SECS.604.3, 606.2.
 11) SHOW THE DISTANCE OF THE CENTERLINE WATER CLOSET
 FROM THE ADJACENT WALL. COMPLY WITH FBC-ACCESS.
 SEC.604.2.
 12) SUBMIT A SANITARY AND WATER RISER FOR REVIEW FOR
 THE NEW PLUMBING WORK TO BE INSTALLED. WPB AMEND. TO
 FBC SEC. 1107.3.5.1.3.
 13) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE ANCHORING
 MATERIAL FOR THE DOWELS AND THE SPACING OF THE DOWELS
 ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE
 TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER
 OVER WELL COMPACTED SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR FINAL INSPECTION.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW