Plan Review Notes For Permit 21061341 |
Permit Number |
21061341 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-07-08 09:59:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS NO SITE PLAN INDICATING THE LOCATION OF THE | | FENCE, HEIGHT OF FENCE, TYPE OF FENCE, NOR ANY PROPOSED | | GATE LOCATIONS AND WIDTHS. | | | | EMERGENCY VEHICLE ACCESS WIDTHS (FIRE LANE) IS 20'. | | | | PLEASE PROVIDE DETAILS AND DIMENSIONS. | | | | 2) KNOX PADLOCKS ARE RECOMMENDED, NO REQUIRED, AT EACH | | GATE FOR FD EMEGENCY ACCESS AND SITE ACCESS. | | | | PLEASE PROVIDE AN APPLICABLE NOTE INDICATING KNOX | | PADLOCKS USE OR NOT. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|