Plan Review Notes For Permit 21061332 |
Permit Number |
21061332 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-07-21 14:09:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED PLANS DO NOT SPECIFICALLY INDICATE | | WHERE THE FIRE LINE UNDERGROUND IS LOCATED. | | | | FOR CLARITY PURPOSES PLEASE PROVIDE HIGHLIGHTS FROM | | STARTING POINT(TAP) TO ENDING POINT(POS) TO INCLUDE FDC | | AND DDCV. | | | | | | 1A) THERE ARE NO PRODUCT SUBMITTALS/MANUFACTURE'S SPEC | | SHEETS. | | | | PLEASE PROVIDE THESE SHEETS INDICATING COMPLIANCE WITH | | NFPA REQUIREMENTS. | | | | | | 2) THERE ARE NO INDICATIONS THAT THE PROPOSED WILL | | COMPLY WITH ANY NFPA CODE, INCLUDING NFPA 24, STANDARD | | FOR THE | | INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR | | APPURTENANCES | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE | | COMPLIANCE. | | | | | | | | 3) DO NOT COVER OVER ANY JOINT PRIOR TO FIRE | | INSPECTION. ALL JOINTS MUST REMAIN VIEWABLE AND | | ACCESSIBLE. | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE | | COMPLIANCE. | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|