2021-08-31 15:53:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21061218
 ADD: 4806 S. DIXIE HWY.
 CONT: MAC ENTERPRISES INC.
 TEL: 561-840-0063
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 31ST/ 2021
 ACTION: DENIED.
 NOTICE ONLY!! 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
 1-2) COMPLIED.
 3) SHEET T.1 TITLE SHEET: THE RESPONSE COMMENT
 INDICATES THE OCCUPANT LOAD HAS ALWAYS BEEN A B /
 BUSINESS OCCUPANCY WITH AN OCCUPANT LOAD OF 49 OR LESS.
  
 3A) 2ND REQUEST. PLEASE REFER TO THE 2020 FBC-B TABLE
 1004.5 FOR BUSINESS IT IS TAKEN AS GROSS. RESPONSE
 STATES SEE LS1. PLEASE NOTE VERSION 2 PLANS THE LOWER
 LEFT HAND OF THE PAGE THE SQ. FT. AND OCCUPANT LOAD WAS
 CHANGED, IT IS THE SAME FLOOR PLAN NOTHING MOVED, THE
 PLANS WERE VERSIONED.
 FLOOR AREA, GROSS. THE FLOOR AREA WITHIN THE INSIDE
 PERIMETER OF THE EXTERIOR WALLS OF THE BUILDING UNDER
 CONSIDERATION, EXCLUSIVE OF VENT SHAFTS AND COURTS,
 WITHOUT DEDUCTION FOR CORRIDORS, STAIRWAYS, CLOSETS,
 THE THICKNESS OF INTERIOR WALLS, COLUMNS OR OTHER
 FEATURES. THE FLOOR AREA OF A BUILDING, OR PORTION
 THEREOF, NOT PROVIDED WITH SURROUNDING EXTERIOR WALLS
 SHALL BE THE USABLE AREA UNDER THE HORIZONTAL
 PROJECTION OF THE ROOF OR FLOOR ABOVE. THE GROSS FLOOR
 AREA SHALL NOT INCLUDE SHAFTS WITH NO OPENINGS OR
 INTERIOR COURTS.
 FOR ASSEMBLY OCCUPANCIES THE OCCUPANT LOAD FACTOR IS
 TAKEN AS NET. FLOOR AREA, NET. THE ACTUAL OCCUPIED AREA
 NOT INCLUDING UNOCCUPIED ACCESSORY AREAS SUCH AS
 CORRIDORS, STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS
 AND CLOSETS.
 1ST ROUND OF COMMENTS. THE SOSO MARKET/ CAF? IS LISTED
 AS A BUSINESS OCCUPANCY. THE INTERIOR OCCUPANT LOAD IS
 CALCULATED AT 55 OCCUPANTS AND SQUARE FOOTAGE OF 1,431
 SQ. FT. THIS TENANT SPACE IS AN A2 OCCUPANCY PER
 SECTION 303.3 OF THE 2020FBC-BUILDING CODE. THE TENANT
 SPACE DOES NOT MEET THE CRITERIA FOR SMALL ASSEMBLY
 AREAS, SECTION 303.1.2.
  
  
 3B) 2ND REQUEST, SAME COMMENT. WITH THE CAFE/
 RESTAURANT MEETING THE CRITERIA FOR AN A-2 OCCUPANCY
 AND EITHER A BUSINESS, OR MERCANTILE OCCUPANCY AS THE
 OTHER MIXED-USE OCCUPANCY TABLE 508.4 FOR
 NON-SPRINKLERED BUILDING A 2 HOUR FIRE RATED FIRE
 BARRIER , NOTED ON SHEET LIFE SAFETY PLAN, NO CUT
 SECTION OF WALL NOR UL LISTING, PROVIDE THE LISTING
 DETAIL FOR ALL MATERIALS THAT MAKE UP THE ASSEMBLY.
  
 3C) 2ND ROUND OF COMMENTS. PLEASE PROVIDE A DETAIL/ CUT
 SECTION OF THE FIRE BARRIER WALL IN ACCORDANCE WITH
 SECTION 707.5 OF THE 2020FBC-BUILDING. FIRE BARRIERS
 SHALL EXTEND FROM THE TOP OF THE FINISH FLOOR TO BELOW
 TO THE UNDERSIDE OF THE ROOF SHEATHING AND CONTINUOUS
 THROUGHOUT ALL CONCEALED SPACES. JOINTS AND
 INTERSECTIONS SHALL COMPLY WITH SECTIONS 707.8 AND
 707.9.
  
 3D) 2ND REQUEST. THE CLASSIFICATION OF WORK IS STATED
 AS RETROFIT. PLEASE REFER TO THE 2020 EXISTING BUILDING
 CODE SECTION 1001.2.2.1. PARTIAL CHANGE IN OCCUPANCY.
 WHERE THE OCCUPANCY CHANGE IS MADE TO A PORTION OF AN
 EXISTING BUILDING SECTION 1012 SHALL APPLY. SEE 1012.1
 THROUGH 1012.8 ACCESSIBILITY.
 3E) SEMI-COMPLIED/ DEPENDING ON THE OCCUPANCY TYPE AND
 OCCUPANT LOAD. THE PROJECT DATA IS MISSING THE PLUMBING
 FIXTURE COUNT LOAD, PLEASE NOTE FOR THE PLUMBING
 FIXTURES THE EXTERIOR SEASONAL SEATING IS TO BE FIGURED
 BRING THE TOTAL OCCUPANT LOAD FOR THE PLUMBING FIXTURES
 TO 88 OCCUPANTS. 2020 FBC-BUILDING TABLE 2902.1.
  
 4) 2ND REQUEST. THE TITLE SHEET DECLARED THIS BUILDING
 IS NON-SPRINKLERED. SECTION 1007.1.1 REQUIRES THE (2)
 REQUIRED EXITS TO BE PLACED NOT LESS THAN ONE-HALF THE
 OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION
 OF THE BUILDING OR AREA SERVED. THE MEASUREMENT 72.833/
 2= 36.41 FEET APART MINIMUM BETWEEN CENTERLINE OF
 DOORWAYS. THIS REVIEW THE DESIGNER OF RECORD SHOWS THE
 HORIZONTAL SEPARATION OF EXIT DOORWAYS CENTERLINE OF
 THE FRONT DOORS AND THE REAR DOOR AT THE KITCHEN.
 PLEASE REVIEW 2020 FBC-B SECTION 1016.2.5. EGRESS SHALL
 NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES.
 1ST ROUND OF COMMENTS. SHEET LS-1 SHOW THE DIAGONAL
 DISTANCE FOR THE CAFE TO BE 72 FT. 10 INCHES. THE TITLE
 SHEET DECLARED THIS BUILDING IS NON-SPRINKLERED.
 SECTION 1007.1.1 REQUIRES THE (2) REQUIRED EXITS TO BE
 PLACED NOT LESS THAN ONE-HALF THE OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA SERVED. THE MEASUREMENT 72.833/ 2= 36.41 FEET
 APART MINIMUM. THE PLAN STATES 31FEET 10 INCHES APART.
 WHEN CALIBRATING THE PLAN FROM THE FURTHEST POINT ON
 BOTH PAIRS OF EXIT DOORS THE MEASUREMENT IS 35.75 FEET
 APART.
  
 4A) THE PLAN DOES NOT INDICATE THAT THERE IS 2
 ACCESSIBLE MEANS OF EGRESS, EXITING. THE FLOOR PLAN
 SHOWS WHAT APPEARS TO BECOME A ACCESSIBLE RAMP, IT
 APPEARS TO LEAD TO A PUBLIC WAY. THE FLOOR PLAN DOES
 NOT SHOW IF THE FRONT DOORS ARE ACCESSIBLE FOR EGRESS
 AND EXITING CAN A PERSON IN A WHEELCHAIR MAKE IT TO THE
 PUBLIC WAY. SEE CHANGES IN LEVEL 2020 ACCESS. CODE 303.
 2. FLORIDA ACCESSIBILITY CODE SECTION: DISPROPORTIONATE
 COST 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% DISPROPORTIONATE
 FUNDS ($13,240.00 DOLLARS) LISTED FOR EACH ELEMENT
 WHERE THE FUNDS ARE BEING SPENT AND IN THE ORDER LISTED
 IN SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2020
 ACCESSIBILITY CODE.
  
 1ST ROUND OF COMMENTS. 2020 FBC-ACCESSIBILITY CODE
 SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4B) COMPLIED. SHEET LS- 1 AND A.1 BOTH SHOW A NEW
 ACCESSIBLE RAMP. A.1 AND A.4 DETAIL 7 BOTH SHOW THE
 UPPER AND LOWER LANDING TO BE 4 FEET LONG. THE 2020
 FBC-B SECTION 1012.6.3 STATES THE RAMP LANDING LENGTH
 IS REQUIRED TO BE 60 INCHES IN LENGTH. PLEASE NOTE THE
 RAMP IS PART OF THE REQUIRED ACCESSIBLE ROUTE (2ND
 MEANS OF EGRESS).
  
 4C) COMPLIED. PLEASE PROVIDE A SITE PLAN SHOWING THE
 NEW ACCESSIBLE RAMP THE L. S. PLAN IT DOES NOT APPEAR
 TO SHOW THE BOTTOM LANDING WHERE AS THE FLOOR PLAN
 SHOWS A SHORT LANDING, IT IS UNKNOWN IF THE RAMP LEADS
 TO THE PUBLIC WAY AND CLEAR OF ANY PARKING SPACES. 2020
 FBC-B SECTION 1028.5 ACCESS TO THE PUBLIC WAY.
  
 5) NEW COMMENT. THE LIFE SAFETY SHEET DOES NOT SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE.
  
 5A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 5B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 5C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 5D) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 5E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  