Plan Review Notes
Plan Review Notes For Permit 21061218
Permit Number 21061218
Review Stop P
Sequence Number 1
Notes
Date Text
2021-07-13 16:29:4007/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A-1;
  
 A. IN RESTROOM 109, THE LAV INS ENCROACHING IN THE
 CLEAR FLOOR SPACE FOR THE CLEAR FLOOR SPACE SHALL BE
 60" INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDEWALL, AND 56? INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1.
  
 B. PLEASE DETAIL OR SHOW ACCESSIBLE DIMENSIONS FOR
 FIXTURE CLEARANCES PER THE FLORIDA BUILDING CODE AND
 FLORIDA ACCESSIBILITY CODE.
  
 2. ON SHEET A-3;
 A. THE PLANS ARE CUT OFF ON THE TOP PART. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. PLEASE SHOW THE TURNING SPACE DIAMETER- SPACE THAT
 SHALL BE A SPACE OF 60 INCHES DIAMETER MINIMUM PER THE
 2020 FBC ACC SEC. 304.3.
  
 C. THE MIRROR'S REFLECTIVE PART NEEDS TO BE 40 INCHES
 TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3.
  
 D. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 E. PLEASE PROVIDE DETAIL ON HOW GRAB BARS REINFORCE IN
 WALLS. WOULD YOU PLEASE SHOW THE MINIMUM AND MAXIMUM
 DISTANCE FROM THE FLOOR PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET P-1;
 STANDARDS FOR ONSITE SEWAGE TREATMENT AND DISPOSAL
 SYSTEMS. A. THE HAND SINKS ARE NOT ALLOWED TO GO INTO
 THE GREASE INTERCEPTOR. PLEASE REFER TO 64E-6, FLORIDA
 ADMINISTRATIVE CODE FOR PROPER DISPLACEMENT TO THE
 SANITARY OR GREASE INTERCEPTOR PER THE 64E-6. THE MOP
 SINK SHALL GO INTO THE GREASE INTERCEPTOR.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON REMARKS?
  
 4. ON SHEET P-2;
 STANDARDS FOR ONSITE SEWAGE TREATMENT AND DISPOSAL
 SYSTEMS. A. PLEASE SHOW THE MOP SINK GOING INTO THE
 GREASE INTERCEPTOR, REFER TO 64E-6, FLORIDA
 ADMINISTRATIVE CODE FOR PROPER DISPLACEMENT TO THE
 SANITARY OR GREASE INTERCEPTOR PER THE 64E-6. THE MOP
 SINK SHALL GO INTO THE GREASE INTERCEPTOR.
  
 B. HAND SINK IN THE KITCHEN AREA ARE SHOWN GOING INTO
 GREASE INTERCEPTORS WHICH ARE NOT ALLOWED; REFER TO
 64E-6, FLORIDA ADMINISTRATIVE CODE FOR PROPER
 DISPLACEMENT TO THE SANITARY OR GREASE INTERCEPTOR PER
 THE 64E-6. STANDARDS FOR ONSITE SEWAGE TREATMENT AND
 DISPOSAL SYSTEMS.
  
 5. ON SHEET P-3;
  
 A. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES
 MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE
 REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1.
  
 B. PLEASE PROVIDE A SHUTOFF VALVE ON BOTH SIDES OF THE
 RECIRCULATING PUMP PER THE 2020 FBC SEC. P 606.2 #3.
 ALSO, SHOW ON HEATER DETAIL P-700 #11.
  
 C. PLEASE PROVIDE A HAMMER ARRESTOR ON THE WARE-WASHER
 AND ANY OTHER QUICK CLOSING VALVE PER THE 2020 FBC SEC.
 604.9.
  
 D. WATER TO EACH STRUCTURE SHALL HAVE A SUPPLY PIPE AT
 THE ENTRANCE INTO THE SHUT-OFF VALVE PER THE 2020 FBC
 606.1 #2 LOCATION OF FULL-OPEN VALVES.
  
 6. ON SHEET P-4, UNDER PLUMBING FIXTURE SCHEDULE FOR
 INLINE BACKFLOW PREVENTER, 1022 ARE FOR SODA MACHINES
 AND WITH A CARBONATION WATER OVERFLOW AND REQUIRE A
 DRAIN PER THE 2020 FBC SEC. 608.17.1.1., THE 1024
 INLINE BACKFLOW PREVENTER ARE FOR ICEMAKER AND COFFEE
 MAKER PER THE 2020 FBC SEC. 608.17.1.2. WOULD YOU
 PLEASE CORRECT WHICH WILL BE USED?
  
 7. ON SHEET P-5; PLEASE PROVIDE DETAIL FOR THE
 MULTIPLE-COMPARTMENT SINK SHOWING THE DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR PER THE 2020 FBC P
 802.1.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  