2021-07-07 13:32:021ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21061218
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 A COMPLETE REVIEW CANNOT BE COMPLETED UNTIL THE
 INFORMATION IS CLEARER AS TO WHAT THIS PERMIT SHALL
 INCLUDE. THERE ARE CONFLICTING DOCUMENTS.
  
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE
 2020 FBC M 403.3.1.1 AND TABLE 403.3.1.1 AND NOT THE
 ARCHITECTURAL OCCUPANT LOAD. THE OUTDOOR AIR
 CALCULATIONS MUST BE CALCULATED BASED ON THE USE OF
 SPACE. ( RTU-1 KITCHEN SHOULD HAVE 182 CFM OF OUTDOOR
 AIR WITH 473 CFM OF EXHAUST; THE TOTAL CFM?S OF OUTDOOR
 AIR FOR RTU-1 SHOULD BE 204 CFM, WHICH IS LESS THAN THE
 600 CFM PROVIDED BUT THE NUMBERS SHOULD BE RIGHT. RTU-2
 DINING-BAR OUTDOOR AIR SHOULD BE 973 CFM, WHICH IS MORE
 THAN THE TOTAL OUTDOOR AIR SHOWN. RTU-3&4 ENERGY
 SUMMARY REPORT PAGE 20 INDICATES THE USE OF EACH SPACE.
 PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON EACH
 USE OF SPACE. FBC 403.3.1.1 AND TABLE 403.3.1.1. BASED
 ON THE ENERGY SUMMARY REPORT AND TABLE 403.3.1.1 THE
 OUTDOOR AIR REQUIRED FOR THIS TENANT SPACE WOULD BE
 1,100 CFM.
  
 2) THE ENERGY SUMMARY REPORT IS FOR A RESTAURANT AND
 FOR THE TENANT UPFIT, IT SHOWS THE USE OF SPACE IN THE
 FUTURE TENANT UPFIT. THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS DOES NOT SHOW THE SAME SPACES. THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOWS THE
 FUTURE TENANT SPACE AS A SHELL .
  
 3) THE EQUIPMENT SIZING CALCULATIONS LISTS RTU-3 AND
 RTU-4 AS PROJECT NAME: S DIXIE CAF? RESTAURANT WPB. THE
 DRAWINGS SHOW THESE TWO UNITS ARE FOR THE FUTURE
 TENANT. PLEASE CLEAR UP THIS PROJECT AND ONLY SHOW THE
 RESTAURANT IN THIS PROJECT.
  
 4) PLEASE PROVIDE STRUCTURAL DRAWINGS FOR THIS PROJECT
 SHOWING HOW THE NEW RTU?S WILL BE SUPPORTED ON THE
 EXISTING ROOF. FBC 107.2.1
  
 5) SHEET M-3: THE RTU-4 IS NOT SHOWN ON THE OUTDOOR AIR
 CALCULATIONS. PLEASE INCLUDE RTU-4 IN THIS TABLE. FBC
 107.2
  
 6) PLEASE SHOW THAT THE NEW RTU?S WILL MEET THE
 CLEARANCE AND FALL PROTECTION. FBC M 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  