2021-06-23 08:04:17PLAN REVIEW ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: NOTE FROM ENGINEER OF RECORD (EOR) STATES NO
 CHANGES SHALL BE MADE TO PLANS WITHOUT HIS APPROVAL.
  
 1. REVISE PG E4. TO REFLECT PROPOSED CHANGES UNDER GEN
 RES PERMIT 21060873. ( REPLACE GENERAC 48KW GEN WITH
 KOHLER 100KW GEN, REMOVE LOAD SHEDDING FROM
 CALCULATIONS, CHANGE CONDUCTOR SIZING FOR GEN TO PANEL
 FROM 3 #300MCM TO 3 4/0, ATS WILL BE 400A SE, SHOW
 CONTROL CIRCUT CONDUCTOR TYPE AND SIZING).
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PLAN PAGE E-1 AND ELECTRICAL SITE PLAN SHOW STANDBY
 GENERATOR OUTSIDE GARAGE. GENERATOR LOCATION SHALL BE
 PER PERMIT 21060873 (GEN-RES). REDLINED PLANS.
  
 NOTICE: REVISED PLAN PAGE E4 WILL REQUIRE VALID DIGITAL
 SIGNATURE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.