2021-07-30 08:24:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THIS PROJECT AS BEING EXPOSURE
 CATEGORY B. THE DEFAULT EXPOSURE CATEGORY IS C. DUE TO
 THE OPEN AREAS OF THE GOLF COURSE, THE LAKES AND CANALS
 THAT ARE IN CLOSE PROXIMITY TO THE PROJECT SHOULD BE
 CONSIDERED EXPOSURE CATEGORY C. IF YOU DISAGREE,
 PROVIDE AN ANALYSIS OF ALL OF THE WIND DIRECTIONS AT
 THE PROJECT THAT WILL SUPPORT YOUR DETERMINATION.
 FBC-R301.2.1.4 EXPOSURE CATEGORY
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 HORIZONTAL ROLLING WINDOW AND THE SLIDING GLASS DOOR DO
 NOT SHOW THAT THEY ARE IN COMPLIANCE WITH THE 2020 FBC.
 THEY ARE ALSO REQUIRED TO BE APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC AMEND. 107.3.4 - PROVIDE TWO
 SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED ON THE
 PLANS, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE METAL ROOFING THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD. FBC AMEND. 107.3.4
  
 4) SHOW COMPLIANCE WITH FBC-R806 FOR ROOF VENTILATION.
  
 5) SPECIFY THE ROOF COMPONENT AND CLADDING PRESSURES ON
 THE PLANS. R301.2.1 WIND DESIGN CRITERIA
  
 6) PROVIDE A FLASHING DETAIL FOR NEW METAL ROOF TO THE
 EXISTING GABLE WALL. FBC-R903.2 FLASHING
  
 7) SUBMIT ENERGY CODE COMPLIANCE FORMS. FBC ENERGY
 COMPLIANCE CHAPTER 4 [RE] RESIDENTIAL ENERGY EFFICIENCY
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  