2021-06-30 15:24:58 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE COVER SHEETS FOR PRODUCT APPROVALS FL26095 |
| AND FL23358. |
| THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE |
| VERSION, AND STATUS, FBC R 301. |
| (COVER SHEETS ARE NOT REQUIRED FOR MIAMI DADE NOAS.) |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 2. PROVIDE A WINDOW SCHEDULE. INCLUDE THE ROUGH OPENING |
| AND ESIGN PRESSURES OF EACH OPENING. |
| |
| 1. LOCATION REFERENCE TO OPENING NUMBER ON PLAN. |
| 2. DEVICE TYPE WINDOW/DOOR/SHUTTER |
| 3. ROUGH OPENING WXH (AREA SF) |
| 4. DESIGN PRESSURES TABLE R301.1.(2) OR ASCE 7-16 |
| 5. NOA OR FL NUMBER |
| 6. MAX DESIGN PRESSURE FROM NOA OR FL |
| 7. IDENTIFY EGRESS OPENINGS |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |