2021-07-09 15:46:121ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21060846
 7/9/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.0: REVISE THE 2020 FBC 7TH EDITION CODE
 SECTION TEXT TO MATCH THE TEXT LISTED UNDER SECTIONS
 454.1.3.1.2, 454.1.3.1.6, AND 454.1.3.1.9. RED LINE
 TEXT HAS BEEN ADDED TO THESE SECTIONS IN THE NEW 2020
 7TH EDITION CODE WHICH IS PERTINENT TO THE DESIGN OF
 THE POOL- SECTION 107.2.1 WPB.
  
 2) P1.1: BASED ON THE FLOOR PLAN DRAWINGS OF THE
 SANITARY FACILITIES FOR THE MAIN POOL AND SPA, IT
 APPEARS THE REQUIRED NUMBER OF PLUMBING FIXTURES HAVE
 BEEN PROVIDED INCLUDING THE 3/2 RATIO OF WOMEN'S WATER
 CLOSETS TO MEN'S WATER CLOSETS AND URINALS. PLEASE NOTE
 COMPLETE PLUMBING AND ACCESSIBILITY REVIEWS FOR THE
 PROPOSED FACILITIES IS NOT BEING PERFORMED AT THIS
 TIME. A SEPARATE PERMIT AND PLANS FOR THE FACILITY ARE
 REQUIRED- SECTION 105.1 & 107.2.1 WPB.
  
 3) P1.1 & P1.2: PLEASE VERIFY THE PROPOSED NEW MEN'S
 AND WOMEN'S RESTROOM FLOORS ARE IN COMPLIANCE WITH
 SECTION 454.1.6.1.3 FBC B AND ARE CONSTRUCTED OF
 CONCRETE OR OTHER NONABSORBENT MATERIALS, WHICH HAVE A
 SMOOTH, SLIP-RESISTANT FINISH, AND SLOPE TO FLOOR
 DRAINS. IT APPEARS A FLOOR DRAIN MAY BE MISSING IN THE
 MEN'S ROOM. PLEASE CLARIFY HOW THE NUMBER OF DRAINS AND
 LOCATIONS ARE BEING DETERMINED- SECTION 107.2.1 WPB.
  
 4) P1.1: PROVIDE WATER SUPPLY PIPING LAYOUT AND RISER
 DRAWINGS FOR INSTALLATION OF THE HOSE BIB AND POOL
 SHOWER- SECTION 602.2 FBC P AND 107.3.5.1.3 WPB. PLEASE
 PROVIDE EQUIPMENT SCHEDULES FOR THE FIXTURES ON THE
 PLAN- SECTIONS 412.3 & 608.16.4.2 FBC P. A) INDICATE
 HOW WATER FROM THE SHOWER WILL BE DRAINED TO AN
 APPROVED PLACE OF DISPOSAL- SECS. 90-126 & 203 WPB CODE
 OF ORDINANCES. PLEASE NOTE THE DETAIL DOES NOT SHOW A
 DRAIN OR FLOOR SLOPE AT SHOWER LOCATION.
  
 5) P1.2: PLEASE INDICATE WITH A MEASUREMENT ON THE PLAN
 THAT THE WET DECK BETWEEN THE MAIN POOL HAS A MINIMUM
 4FT. UNOBSTRUCTED WIDTH- SECTION 454.1.3.1.3 FBC P.
  
 6) P1.2: INDICATE THE ACTUAL SLOPE OF THE WET DECK
 BETWEEN THE MAIN POOL AND ADULT POOL. DO NOT PROVIDE A
 MINIMUM OR MAXIMUM. REFER TO SECTION 454.13.1.2 FBC B
 AND SECTION 403.3 FBC ACC FOR CROSS SLOPE LIMITATION.
  
 7) P1.2: INDICATE THE WIDTH OF THE DECK SLOPE AT THE
 ZERO DEPTH ENTRY- SECTION 454.1.9.6.3 FBC B.
  
 8) P1.1: LABEL THE LOCATIONS OF THE MAIN POOL AND SPA
 POOL LIFTS AND SHOW THE REQUIRED CLEAR DECK SPACES-
 SECTIONS 242.2, 1009.2.1, & 1009.2.3 FBC ACC, AND
 SECTION 454.1.2.5.6 FBC B.
  
 9) P1.0: THE POOL LIFT INFORMATION UNDER SPLASH SERIES
 INDICATES THE LIFTS ARE THIRD PARTY TESTED & VERIFIED
 ADA COMPLIANT AND STATE OF CALIFORNIA COMPLIANT. PLEASE
 SUBMIT CERTIFICATION DOCUMENTATION THE LIFTS ARE TESTED
 AND VERIFIED ADA COMPLIANT FOR USE IN THE STATE OF
 FLORIDA. PLEASE MARK OR HIGHLIGHT WHICH MODEL IN THE
 SCHEDULE IS PROPOSED TO BE INSTALLED- SECTION 107.2.1
 WPB.
  
 10) P1.0: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION GUIDELINES FOR THE PROPOSED LIFTS WITH
 APPROVAL STAMPS BY THE ENGINEER OF RECORD- SECTION
 107.3.4 WPB.
  
 11) P1.0: PLEASE PROVIDE ON THE PLANS OR ON
 SUPPLEMENTAL PLANS ENLARGED INSTALLATION DETAILS FOR
 THE LIFTS THAT INDICATE COMPLIANCE WITH SECTIONS
 1009.2.2 SEAT LOCATION, 1009.2.3 CLEAR DECK SPACE,
 1009.2.4 SEAT HEIGHT, 1009.2.5 SEAT WIDTH, 1009.2.6
 FOOTRESTS AND ARMRESTS, 1009.2.7 OPERATION. A) VERIFY
 COMPLIANCE WITH SECTION 1009.2.9 LIFTING CAPACITY.
 SINGLE PERSON POOL LIFTS SHALL HAVE A WEIGHT CAPACITY
 OF 300 POUNDS MINIMUM AND BE CAPABLE OF SUSTAINING A
 STATIC LOAD OF AT LEAST ONE AND A HALF TIMES THE RATED
 LOAD.
  
 12) MS5.3, MS5.4, MP6.4, MP6.5: PROVIDE A CIVIL PLAN OR
 SITE UTILITY PLAN SHOWING HOW WATER IS BEING SUPPLIED
 TO THE POOL AND SPA AND THE LOCATION OF THE REQUIRED
 BACKFLOW PREVENTERS- SECTIONS 454.1.6.3 FBC B AND
 SECTION 608.7 FBC P. PLEASE CLARIFY IF THE WATER SUPPLY
 LINES TO THE COLLECTOR TANKS ARE ALSO THE MAIN WATER
 SUPPLY LINES TO THE POOL AND SPA- SECTION 454.1.6.5.11
 FBC B. PLEASE NOTE THAT FL. LICENSED PLUMBING
 CONTRACTORS SHALL OBTAIN SEPARATE PERMITS FOR
 INSTALLATION OF THE WATER LINES AND AUTO FILL DEVICES,
 AND FOR THE REQUIRED BACKFLOW PREVENTERS IN ACCORDANCE
 WITH FL. STATUTE 489.105, SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. PLEASE INCLUDE PLUMBING
 PIPING DETAILS IN COMPLIANCE WITH SECTION 606 FBC P.
  
 13) MS5.3, MS5.4, MP6.4, MP6.5: PROVIDE A CIVIL PLAN OR
 SITE UTILITY PLAN SHOWING HOW WASTE WATER FROM THE POOL
 AND SPA WILL BE DRAINED TO AN APPROVED PLACE OF
 DISPOSAL- SECTION 454.1.6.5.15 FBC B, AND SECS. 90-126
 & 203 WPB CODE OF ORDINANCES. PLEASE INCLUDE PLUMBING
 PIPING DETAILS IN COMPLIANCE WITH SECTION 704 FBC P.
  
 14) MS5.3, MS5.4, MP6.4, MP6.5: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR RECIRCULATION AND TREATMENT
 EQUIPMENT INCLUDING THE FILTERS, CHEMICAL CONTROLLER,
 SALT CHLORINE GENERATOR, AND TREATMENT FEEDERS SHOWING
 THE EQUIPMENT CONFORMS WITH REQUIRED STANDARDS NSF/ANSI
 STANDARD 50, CIRCULATION SYSTEM COMPONENTS AND RELATED
 MATERIALS FOR SWIMMING POOL, SPAS/HOT TUBS, DATED APRIL
 2007- SECTION 454.1.6.5.1 FBC B.
  
 15) MS5.0 & MP6.0: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE MAIN DRAINS AND COVERS SHOWING CONFORMANCE WITH
 THE ANSI/APSP 16 STANDARD- 454.1.6.5.10.2 FBC P.
 PROVIDE AN ENLARGED MAIN DRAIN DETAIL IN COMPLIANCE
 WITH SECTION 454.1.6.5.10.2 FBC B.
  
 16) MS5.0 & MS5.2: PROVIDE AN EQUALIZER INSTALLATION
 DETAIL- SECTION 454.1.6.5.3.2.3 FBC B.
  
 17) MS5.3 & MS5.4: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SPA RECIRCULATION PUMP, THERAPY PUMP, COLLECTOR
 TANK, AND CARTRIDGE FILTER- SECTIONS 454.1.6.5.4,
 454.1.6.5.5, & 454.1.6.5.10.5 FBC P.
  
 18) MS5.3 & MS5.4: PROVIDE TOTAL DYNAMIC HEAD
 CALCULATIONS TO VERIFY PUMP SIZING AND PUMP SELECTION
 SHOWN IN THE PUMP CURVE- SECTION 454.1.6.5.4 FBC B. THE
 CALCULATIONS SHALL INCLUDE THE CALCULATED HEAD FOR
 PIPING AND EQUIPMENT.
  
 19) MS5.0 & MS5.4: SHOW THE FLOW VELOCITIES OF THE
 PRESSURE PIPING AND THE SUCTION PIPES FROM THE PUMPS TO
 THE COLLECTOR TANK IN THE PIPING DIAGRAM- SECTION
 454.1.6.5.8 FBC B.
  
 20) MS5.0: PLEASE NOTE THAT THE PIPING DIAGRAM SHOWS A
 420 GPM FLOW RATE FOR THE MAIN DRAIN HOWEVER THE DESIGN
 SPECIFICATIONS INDICATE A 180 GPM FLOW RATE- PLEASE
 CORRECT OR PROVIDE AN EXPLANATION- SECTION
 454.1.6.5.3.2.1 FBC B.
  
 21) MS5.0 & MS5.4: SHOW THE SOURCE OF THE THERAPY AIR
 AND PROVIDE EQUIPMENT LOCATION AND SPECIFICATIONS-
 SECTION 454.1.8.6.1 FBC B.
  
 22) MS5.0 & MS5.4: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SPA INLETS- SECTION 454.1.6.5.9 FBC B.
  
 23) MP6.1: SHOW THE SPACING MEASUREMENTS BETWEEN THE
 INLETS AND ADJACENT WALLS- SOME APPEAR TO BEYOND THE
 MAXIMUM 10 FT. DISTANCE- SECTION 454.1.6.5.9.4 FBC P.
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL
 INLETS- SECTION 454.1.6.5.9 FBC B.
  
 24) MP6.0, MP6.1 & MP6.3: THE AQAUWAVE RETURN INLETS
 APPEAR TO BE NON-COMPLIANT WITH SECTION 454.1.6.5.9
 BECAUSE THEY ARE POSSIBLY HAZARDOUS PROTRUSIONS AND ARE
 NOT INSTALLED A MINIMUM OF 12 INCHES BELOW THE NORMAL
 OPERATING POOL LEVEL AS REQUIRED.
  
 25) MP6.1: THE PLAN CALLS OUT 35 MAIN RETURN INLETS
 HOWEVER THE DRAWING APPEARS TO INDICATE MORE THAN THAT
 AMOUNT. PLEASE CLARIFY LOCATIONS OF ALL MAIN POOL
 INLETS- SECTION 107.2.1 WPB.
  
 26) MP6.1: THE PLAN DOES NOT APPEAR TO BE IN COMPLIANCE
 WITH SECTION 454.1.9.6.5 FBC B WHICH REQUIRES ADDITONAL
 RETURN INLETS IN AREAS OF 18 INCHES DEEP, AND DOUBLE
 THE FLOW RATES IN THE AREA.
  
 27) MP6.0 & MP6.3: THE EQUIPMENT LIST CALLS OUT A
 PENTAIR GUTTER MODEL BUT THE DETAIL CALLS OUT HAYWARD.
 PLEASE CORRECT PROVIDE ADDITIONAL NOTES AT THE GUTTER
 DETAIL INDICATION COMPLIANCE WITH SECTION 454.1.6.5.3.1
 PERIMETER OVERFLOW GUTTERS: THE LIP OF THE GUTTER SHALL
 BE UNIFORMLY LEVEL WITH A MAXIMUM TOLERANCE OF 1/4 INCH
 (6 MM) BETWEEN THE HIGH AND LOW AREAS. THE BOTTOM OF
 THE GUTTER SHALL BE LEVEL OR SLOPE TO THE DRAINS.
  
 28) MP6.0 & MP6.3: PLEASE MODIFY THE EQUALIZER LINE
 INLET DETAIL TO SHOW A SPRING-LOADED CHECK VALVE WILL
 BE INSTALLED THAT WILL NOT ALLOW DIRECT SUCTION ON THE
 LINE, AND A PROTECTIVE COVER WILL BE INSTALLED THAT
 CONFORMS TO ASME/ANSI A112.19.8- SECTION
 454.1.6.5.3.2.3 FBC B.
  
 29) MP6.4 & MP6.5: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE RECIRCULATION PUMP, AND THE AQUAWORX D.E.
 FILTER COLLECTOR TANK- SECTIONS 454.1.6.5.4,
 454.1.6.5.5.3, 454.1.6.5.5, & 454.1.6.5.10.5 FBC B.
  
 30) MP6.4 & MP6.5: REFER TO SECTION 454.1.6.5.15 FBC B
 AND SHOW THE LOCATIONS OF THE D.E. SEPARATOR TANKS
 (MPM). SUBMIT MANUFACTURER'S SPECIFICATIONS AND PROVIDE
 INSTALLATION DETAILS ON THE PLANS. D.E. SEPARATOR TANKS
 SHALL HAVE A CAPACITY AS RATED BY THE MANUFACTURER,
 EQUAL TO THE SQUARE FOOTAGE OF THE FILTER SYSTEM. ALL
 LINES SHALL BE SIZED TO HANDLE THE EXPECTED FLOW. THERE
 SHALL NOT BE A DIRECT PHYSICAL CONNECTION BETWEEN ANY
 DRAIN FROM A POOL OR RECIRCULATION SYSTEM AND A SEWER
 LINE. PLEASE NOTE THEN MEANS OF FINAL DISPOSAL MUST BE
 ACCEPTABLE TO THE CITY OF WEST PALM BEACH BUILDING
 DEPARTMENT AND THE UTILITIES DEPARTMENT.
  
 31) MP6.4 & MP6.5: PLEASE IDENTIFY ALL EQUIPMENT IN THE
 INDOOR ROOM AND OUTDOOR AREA THAT ARE RELATIVE TO THE
 SCHEDULE ON THE PLAN- SECTION 107.2.1 WPB.
  
 32) MP6.1, MP6.4 & MP6.5: REFER TO SECTION 454.1.6.5.12
 FBC B AND CLARIFY IF A PLUMBED-IN VACUUM CLEANING
 SYSTEM WILL BE INSTALLED OR A PORTABLE SYSTEM. PROVIDE
 DETAILS AND SPECIFICATIONS FOR PLUMBED-IN SYSTEMS.
  
 33) MP6.4 & MP6.5: SHOW THE FLOW VELOCITIES OF THE MAIN
 DRAIN, GUTTER LINE, AND EQUALIZER LINE PIPING ON THE
 PLANS AND DIAGRAM- SECTION 454.1.6.5.8 FBC B.
  
 34) P1.0, MP6.0: BASED ON THE PLAN NOTE ON P1.0, PLEASE
 INDICATE IF A TIME CLOCK WILL BE INSTALLED, AND THAT IF
 IT IS INSTALLED, THE RECIRCULATION SHUT DOWN TIME WILL
 NOT REDUCE THE POOL TURNOVER RATE TO LESS THAN A
 MINIMUM OF FOUR TURNOVERS OF THE POOL VOLUME PER DAY.
 CONSIDERING THE POOL IS DESIGNED AT A 650 GPM FLOW AT A
 4.5 HOUR TURNOVER TIME- FOUR TURNOVERS PER DAY AT 4.5
 HOURS EA. = 18 HOURS OF RECIRCULATION OPERATION TIME
 REQUIRED. THE NOTE INDICATES THE TIMER MAYL LIMIT
 OPERATION TO 3 HOURS BEFORE OPENING AND 3 HOURS AFTER
 CLOSING, HOWEVER THE POOL RULES INDICATE THE POOL IS
 ONLY OPEN FROM DAWN TO DUSK WHICH SECTION 454.1.6.5.2
 FBC B. PLEASE REVISE THE NOTE TO INDICATE THE ACTUAL
 NUMBER OF HOURS PER DAY THAT THE RECIRCULATION SYSTEM
 WILL RUN.
  
 35) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING SECTIONS
 FROM THE FBC EC:
 C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS
 SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF
 SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED
 ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND
 WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH
 SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS.
 C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL
 METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS
 AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE
 INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP
 MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1.WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
 2.PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY
 POOL HEATING SYSTEMS.
 C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 36) P2.0, AP2.0: PLEASE NOTE THAT SEPARATE PERMITS ARE
 REQUIRED FOR INSTALLATION OF THE POOL HEATER AND GAS
 PIPING, THE POOL RESTROOM/EQUIPMENT ROOM BUILDING, THE
 POOL FENCE, AUTO FILL WATER LINE AND BACKFLOW
 PREVENTER, SITE DRAINAGE PIPING, AND THE INSTALLATIONS
 OF THE HOSE BIBS AND POOL SHOWER- SECTION 105.1 &
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  