2021-07-18 15:59:40WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21060780
 ADD: 1801 S. FLAGLER DR. # 903
 CONT: MASTER CONTRACTORS
 TEL: 561-712-8898
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JULY 18TH/ 2021
 ACTION: DENIED
 1) COVERSHEET:
  
 1A) LISTING FOR WIND DESIGN IS GIVEN AS 2020 ASCE-7-10.
 PLEASE NOTE IN THE 2020 FBC-BUILDING CODE THE REFERENCE
 STANDARD IS ASCE- 7-16. UP DATE PLANS.
  
 1B) UNDER THE ASCE-7 STANDARD THE BUILDING HEIGHT IS
 GIVEN AT 200 FT IN HEIGHT, AND THE BUILDING
 CLASSIFICATION TYPE AS I-B.
 PLEASE NOTE THIS IS A 18 STORY BUILDING. THE HEIGHT OF
 200 FT AND 18 STORY BUILDING WOULD MAKE THIS
 CONSTRUCTION TYPE I-A, SEE THE 2020 FBC-BUILDING TABLES
 504.3 & 504.4. PLEASE UPDATE THE PLAN.
  
 1C) UNDER THE LISTED ASCE-7 THE EXPOSURE GIVEN IS A C
 EXPOSURE. SUBMITTED ON THIS SHEET IS A SATELLITE
 AERIAL. THE LOCATION OF THE UNIT IS NOT IDENTIFIED/
 LOCATED. WITHOUT THIS INFORMATION THE EXPOSURE CAN NOT
 BE DETERMINED NOR IF THE UNIT IS LOCATED IN WALL ZONE 4
 OR WALL ZONE 5 WITH HIGHER PRESSURES. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED TO BE ABLE TO
 DETERMINE EXPOSURE TYPE AND ASSOCIATED PRESSURES.
  
 1D) DESIGN PRESSURES FOR EXPOSURE C BUILDINGS UP TO 60
 FT. IN HEIGHT WORST CASE ALL OPENINGS, (ZONE 5) 10 SQ.
 FT. +50.6/
 -67.8 PSF VASD.
  
 2) SHEET A-1 THE CONSTRUCTION PLAN. THE FLOOR PLAN
 UNDER THE SCOPE OF WORK NOTE 4 NEW FLOORING AS PER PLAN
 SEE SHEET
 A-1. THE FLOOR PLAN ONLY STATES INSTALL NEW FLOORING,
 NO MENTION OF TYPE OF MATERIAL NOR SOUND UNDERLAYMENT.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2D) THE FLOOR PLAN IS SILENT IF TILE IS GOING TO BE
 INSTALLED ON THE BALCONY. IF TILE IS TO BE INSTALLED ON
 THE BALCONY, THEN A ENGINEER WILL NEED TO INSPECT THE
 BALCONY SLAB FOR CRACKS, SPALLING OF STEEL AND HOW TO
 CORRECT THE SPALLED CONCRETE. THE ENGINEER IS TO
 PROVIDE A SIGNED SEALED REPORT AS TO THE CONDITION OF
 THE BALCONY SLAB AND IF REPAIRS ARE NECESSARY HOW THEY
 WILL BE ACCOMPLISHED. NOTE THIS IS A HIGHRISE BUILDING/
 THRESHOLD INSPECTOR (S. I.) REQUIRED.
  
 3) SHEET A-1 THE MASTER BATHROOM THE TUB IS REMOVED,
 AND THE SHOWER IS EXPANDED. NO MENTION OF THE CODE
 ISSUES LISTED BELOW:
  
 3A) NO MENTION OF HOW THE TUB FLOOR BOX OUT FOR DRAIN
 IS TO COMPLY WITH: THROUGH-PENETRATIONS FIRESTOP
 SYSTEMS (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR
 PENETRATION IS MADE FOR THE FUTURE SHOWER DRAIN, THEN
 YOU NEED TO SHOW COMPLIANCE WITH THE 2020 FBC-B SECTION
 714.5.1.2. THROUGH-PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). THROUGH PENETRATIONS SHALL BE
 PROTECTED BY A THROUGH PENETRATION FIRESTOP SYSTEM
 INSTALLED IN ACCORDANCE WITH ASTM E814 OR UL 1479. THE
 SYSTEM SHALL HAVE AN F RATING / T RATING OF NOT LESS
 THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED RATING OF
 THE FLOOR PENETRATED.
  
 3B) THE ENLARGED SHOWER THE NEW FLOOR DRAIN AND SIZE OF
 THROUGH PENETRATION, POST TENSION SLAB/ NEW HOLES. THE
 PLAN IS SILENT AS IF THE LOCATION OF THE EXISTING TUB
 DRAIN IS GOING TO BE REUSED IN THE SAME LOCATION. IF
 NOT, THEN THE FLOOR SLAB WILL NEED TO BE X-RAYED TO
 FIND THE POST TENSION CHORD LOCATIONS. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3C) THE TYPE OF TILE BACKING FOR THE SHOWER. 2020 FBC-B
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALLS AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATIONS. WATER RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 3D) IN THE SHOWER THE HEIGHT OF TILE? 2020 FBC-B
 SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS AND BATHTUBS
 WITH INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72
 INCHES ABOVE THE DRAIN INLET.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL
 MY WORK HOURS ARE MON. & TUES. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT