2021-06-29 17:40:03 | 06/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE TOTAL DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM |
| SYSTEM FLOW HAVE A HEATER AND A CHLORINATOR. THE TDH |
| CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS |
| THAT ARE TO BE INSTALLED. PLEASE CORRECT PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. PLEASE SHOW ON THE POOL PUMP CURVE. IDENTIFY ON THE |
| PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP |
| BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM |
| THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER |
| THE ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. |
| INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR THE |
| PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB AMEND. |
| TO FBC SEC. 107.2.1. |
| |
| 3. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| THE HEATER AND CHLORINATOR IF USED PER THE WPB |
| AMENDMENTS TO FBC SEC. 107.2.1. |
| |
| 4. ON-PAGE ONE, UNDER THE NOTES, AN OVERFLOW LINE IS |
| MENTIONED. IS THAT A POOL FILL, AND IF SO, IT WILL |
| REQUIRE A PVB BACKFLOW. PLEASE CLARIFY PER THE WPB |
| AMENDMENTS TO FBC SEC. 107.2.1. |
| |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |