2021-06-25 16:28:14 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| PERMIT- 21060576 |
| 6/25/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS 1 & 3: NO CHLORINATOR IS SPECIFIED HOWEVER |
| FRICTION LOSS FOR CHLORINATOR IS INCLUDED IN THE TDH |
| CALCULATIONS. PLEASE REVISE THE SCHEDULE OR THE |
| CALCULATIONS- ANSI/APSP/ICC 7- 2013 SECS 4.4.9, |
| 4.4.9.1. |
| |
| 2) SHEET 3: PLEASE PROVIDE THE POOL PUMP CURVE ON THE |
| PLAN AND IDENTIFY ON THE POOL PUMP CURVE WHICH CURVE |
| KEY IS SPECIFIC TO THE PUMP BEING INSTALLED ON THE |
| POOL- ANSI/APSP/ICC 7- 2013 SECS 4.4.9, 4.4.9.1. |
| |
| 3) SHEET 3: PROVIDE A MAIN DRAIN PIPING DETAIL THAT |
| INDICATES THE MAKES AND MODELS OF THE DRAINS AND DRAIN |
| COVERS AND THE FLOW RATES THROUGH THE COVERS, DRAIN |
| PORTS AND THE BRANCH PIPES- ANSI/APSP/ICC 7. PLACE A |
| NOTE TO INDICATE THE DRAIN COVERS SHALL CONFORM TO |
| ASME/ANSI A112.19.8. |
| |
| 4) SHEET 3: INDICATE HOW THE POOL WILL BE FILLED. |
| CLARIFY IF TO IT WILL BE FILLED FROM A HOSE BIB OR |
| CONNECTION TO THE MAIN POTABLE WATER SERVICE- SECTION |
| R4501.9 FBC RES. PLEASE NOTE THAT BACKFLOW PREVENTERS |
| INSTALLED UNDER SEPARATE PERMIT WILL BE REQUIRED FOR |
| CONNECTION TO THE POTABLE WATER SERVICE- SECTION |
| P2902.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |