Plan Review Notes
Plan Review Notes For Permit 21060503
Permit Number 21060503
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-18 09:07:19****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ARE REQUIRED PRIOR TO ISSUANCE OF A DEMO
 PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 2) UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION. THIS RELEASE NEEDS TO
 COME FROM FLORIDA PUBLIC UTILITIES ON THEIR FORM.
  
 3) PLEASE PROVIDE THE METHOD OF WATER DOWN DURING
 DEMOLITION:
 A) IF A WATER TRUCK IS DESIRED, PROVIDE A LETTER
 STATING THE GALLON CAPACITY OF WATER TANK AND A
 STATEMENT THAT THE WATER USED WILL BE POTABLE WATER
 FROM AN OFF-SITE LOCATION ONLY AND THE WATER TRUCK WILL
 BE ON-SITE AT ALL TIMES DURING DEMOLITION.
 B) IF A HYDRANT METER IS DESIRED THAN A
 PERMIT/REGISTRATION NEEDS TO BE OBTAINED FROM THE CITY
 OF WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT.
 C) IF A BACK FLOW PREVENTER IS DESIRED, THEN A SEPARATE
 BACKFLOW PERMIT INCLUDING THE FINAL INSPECTION FROM THE
 BUILDING DEPARTMENT (PLUMBING) IS REQUIRED.
 IF SELECTING THE BACKFLOW OPTION; BEFORE SCHEDULING THE
 FINAL PLUMBING INSPECTION, THE BACKFLOW DEVICE NEEDS TO
 BE TESTED AND CERTIFIED BY THE PUBLIC UTILITIES
 DEPARTMENT, 561 822 2244.
  
 4) THE SEWER LATERAL CAPPING PERMIT HAS BEEN OBTAINED
 (21060646). THE APPROVED FINAL PLUMBING INSPECTION IS
 REQUIRED.
  
 6) PLEASE COMPLETE AND UPLOAD THE DEMO DEBRIS REMOVAL
 FORM. IF THE FORM IS NOT AVAILABLE ON LINE, SEND A
 REQUEST FOR THE FORM TO [email protected].
  
 9) PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEB-SITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THE NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBEST-DEMOLITION-RE
 NOVATION.HTML
  
  
  
  