Plan Review Notes
Plan Review Notes For Permit 21060498
Permit Number 21060498
Review Stop B
Sequence Number 2
Notes
Date Text
2021-07-02 08:59:19PLAN REVIEW COMMENTS
 NOTE: BUILDING STOP 1 WAS LOCKED.
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
 SOME OF THE REQUIRED INFORMATION LISTED BELOW HAS NOT
 BEEN PROVIDED. SUBMIT ALL THAT APPLY AND HAVE NOT BEEN
 PROVIDED.
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  
  
 FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
  
 FBC 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  