Plan Review Notes For Permit 21060421 |
Permit Number |
21060421 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-06-11 14:58:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET ALS 1.1 - FOR CLARIFICATION PURPOSES: THE CODE | | ANALYSIS INDICATES A BUSINESS OCCUPANCY/ BUSINESS | | OFFICE = 1 PR "50 GROSS; AREA = 3043; OCCCUPANCY LOAD = | | 20 PERSONS. | | | | THE FLOOR PLAN LAYOUT INDICATES 41 SEATS. | | | | THE FFPC PROVIDES FOR CONCENTRATED BUSINESS USE @50/SQ | | FT. | | | | BASED ON THE SQ FT INDICATED = 61 | | | | BASED ON BUSINESS USE OTHER @150/SF = 21 | | | | PLEASE REVIEW AND PROVIDE CORRECTIONS OR EXPLANATION IN | | COMPLIANCE WITH THE CODE. | | | | | | 1A) SHOULD THE OCCUPANCY LOAD BE CHANGED TO 61, THE | | OFFICE DOOR NEEDS TO SWING IN THE PATH OF EXT TRAVEL. | | | | PLEASE CORRECT AS APPLICABLE. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|