Date |
Text |
2021-07-08 17:00:39 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21060421 |
| ADD: 205 DATURA ST. # 300 |
| CONT: RICHARD J. TAYLOR |
| TEL: 561-394-5450 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JULY 8, 2021 |
| ACTION: DENIED |
| 1) THE LIFE SAFETY SHEET: |
| 1A) THE CODE ANALYSIS STATES THIS TENANT SPACE IS AN |
| BUSINESS OCCUPANCY. THE PLAN DOES NOT DECLARE THE |
| OCCUPANT LOAD IS TAKEN FROM TABLE 1004.5 BUT THE |
| OCCUPANT LOAD FACTOR IS STATED AT 150, AS IN TABLE |
| 1004.5 AND THE OCCUPANT LOAD OF 20. IT SHOULD BE |
| ROUNDED UP TO 21. 3,043/ 150= 20.28 OCCUPANTS. YOU |
| ALWAYS ROUND UP TO THE NEXT WHOLE OCCUPANT. WHEN YOU |
| ARE ESTABLISHING THE OCCUPANT LOAD BY GIVING THE |
| OCCUPANT LOAD FACTOR OR BY STATING THE TABLE 1004.5 AS |
| THE DESIGNER YOU ARE ESTABLISHING THE DESIGN OCCUPANT |
| LOAD. IF YOU COUNT EVERY CHAIR IN THE TENANT SPACE |
| THERE ARE MORE THAN 50 CHAIRS WHICH WOULD REQUIRE 2 |
| MEANS OF EGRESS. WHAT I BELIEVE AS THE DESIGNER OF |
| RECORD PLEASE REVIEW SECTION 1004.2 FOR INCREASED |
| OCCUPANT LOAD AND SEATING DIAGRAM, FLOOR PLAN, THE |
| POSTING OF THE INCREASED OCCUPANT LOAD 49 OCCUPANTS |
| WITH DIAGRAM / FLOOR PLAN. THIS WILL PROVIDE AN |
| INCREASE OF OCCUPANTS AND STILL MEET THE REQUIREMENTS |
| OF TABLE 1006.2.1 OF NO MORE THAN 49 OCCUPANTS AND A |
| MAXIMUM COMMON PATH OF TRAVEL OF 100 FEET/ SPRINKLERED |
| BUILDING. |
| |
| 2A) FROM THE P1.1 SHEET THE PRIVATE BATHROOM LOOKS TO |
| BE NEW SINCE THERE ARE NEW SANITARY LINES THAT WILL TIE |
| INTO EXISTING LINES. POST TENSION SLAB/ NEW HOLES. THE |
| PLAN IS SILENT AS IF THE LOCATION OF THE EXISTING TUB |
| DRAIN IS GOING TO BE REUSED IN THE SAME LOCATION. IF |
| NOT, THEN THE FLOOR SLAB WILL NEED TO BE X-RAYED TO |
| FIND THE POST TENSION CHORD LOCATIONS. 107.2.1.2. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| PENETRATED. |
| |
| 3) SHEET A1.1 & A3.2. NEW PRIVATE BATHROOM SHOWER AND |
| WATER CLOSET WILL STILL REQUIRE BACKING FOR GRAB BARS, |
| 604.5 EXCEPTION 1 INSTALLED AT THE CORRECT HEIGHTS. |
| |
| 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |