2021-06-08 15:12:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 A.ACCESSIBILITY
 1.STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES MINIMUM WIDE PER FBC ACC 608.2.2. PER WPB FBC
 107.2.1, PROVIDE DIMENSION ON A3.1 ENLARGED PLAN.
  
 2.PER FBC 107.2.1, PROVIDE NOTE ON A3.1; THRESHOLDS IN
 ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 1/2 INCH HIGH
 MAXIMUM IN ACCORDANCE WITH FBC ACC 303.
  
 3.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 REVIEW THE FOLLOWING AND
 PROVIDE/REVISE PLAN AND ELEVATION DETAILS AS REQUIRED
 FOR TOILET ROOMS AND OTHER ACCESSIBLE FIXTURES:
 3A)THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE "16 INCHES MINIMUM TO 18
 INCHES MAXIMUM" FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 3B).THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2. TO BE
 CLEAR, THE 6 INCHES NOTED FROM THE SIDE WALL TO THE
 GRAB BAR IS SUBDECT TO FLUCTUATION BASED ON THE ACTUAL
 CENTERLINE OF THE WATER CLOSET ("16 INCHES MINIMUM TO
 18 INCHES MAXIMUM"), SO THE 6 INCH MEASUREMENT SHOULD
 BE NOTED MAXIMUM OR DELETED ENTIRELY.
 3C)FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 3D)TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE "7 INCHES MINIMUM AND 9 INCHES MAXIMUM" IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 3E)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE "17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM" MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 3F)PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, "33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM" ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 3G)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
  
  
  
 B.PLUMBING
 1.PROVIDE VENT FOR THE MOST DOWNSTREAM WATER CLOSET PER
 FBC PL 909.1. PER FBC PL 912.1, ONLY BATHROOM GROUP
 FIXTURES MAY CONNECT TO THE WET VENT. HD-1 AND SK-1 ARE
 NOT CONSIDERED BATHROOM GROUP FIXTURES (SEE FBC PL
 CHAPTER TWO, DEFINITIONS.)
  
 2. PER WPB FBC 107.2.1, PROVIDE A UL ASSEMBLY FOR NEW
 WALL PENETRATION(S) FROM COMMON AREA(S) TO TENANT
 SPACE(S). COMPLY WITH FBC CHAPTER 7.
  
 3.P2.1; NOTE 2: PER WPB FBC 107.2.1,
 A) PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR THE EWC-1, ICE MAKER, FILTRATION SYSTEM,
 WOULD INDICATE THEY ARE PROVIDED WITH INTERNAL BACKFLOW
 PREVENTION DEVICES. IF EQUIPMENT DOES NOT MEET THE
 CRITERIA NOTED, THEN PROVIDE LEAD FREE BACKFLOW
 PREVENTION DEVICES TO COMPLY WITH FBC PL SECTION 608.
 B) PROVIDE A SCHEMATIC TO CLEARLY SHOW THE COLD WATER
 FLOW TO ALL OF THE DEVICES, EQUIPMENT AND FIXTURES.
 SHOW PLACEMENT OF BACKFLOW PREVENTER, VALVES AND WATER
 FILTER AS THEY RELATE TO ALL OF THE DEVICES, EQUIPMENT
 AND FIXTURES.
  
 4.PER FBC PL 606.1(5), PROVIDE FULL OPEN VALVES AT THE
 TOP OF THE WATER DOWN FEED PIPES.
  
 5.PER FBC PL 606.1(2), PROVIDE FULL OPEN VALVE UPSTREAM
 OF COMMON/TENANT WALL PENETRATION TO BE ACCESSIBLE TO
 BUILDING MAINTENANCE AT ANYTIME.
  
 6.PER FBC PL 606.2, PROVIDE SEPARATE SHUT OFF VALVE FOR
 HOT AND COLD TO FIXTURE (SINK OR LAVATORY) AND TO THE
 TANKLESS WATER HEATER
  
 7.P4.1; PLUMBING FIXTURE CONNECTION SCHEDULE: PER FBC
 PL TABLE 709.1, FIXTURE DRAINS AND TRAP SIZE FOR SINKS
 SHALL BE MINIMUM 1-1/2 INCH.
  
 8.PER WPB FBC 107.2.1, PROVIDE A SHOWER WALL/DRAIN AND
 THRESHOLD DETAIL. PROVIDE ON THE DETAIL THE FOLLOWING
 INFORMATION:
 3A)FBC PL 421.3 SHOWER WASTE OUTLET.
 WASTE OUTLETS SERVING SHOWERS SHALL BE NOT LESS THAN
 1-1/2 INCHES (38 MM) IN DIAMETER AND, FOR OTHER THAN
 WASTE OUTLETS IN BATHTUBS, SHALL HAVE REMOVABLE
 STRAINERS NOT LESS THAN 3 INCHES (76 MM) IN DIAMETER
 WITH STRAINER OPENINGS NOT LESS THAN 1/4 INCH (6.4 MM)
 IN LEAST DIMENSION. WASTE OUTLETS SHALL BE FASTENED TO
 THE WASTE PIPE IN AN APPROVED MANNER.
 3C)FBC PL 421.5 SHOWER FLOORS OR RECEPTORS.
 FLOOR SURFACES SHALL BE CONSTRUCTED OF IMPERVIOUS,
 NONCORROSIVE, NONABSORBENT AND WATERPROOF MATERIALS.
 3D)FBC PL 421.5.1 SUPPORT.
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
 3E)FBC PL 421.5.2SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER-TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 421.5.2.1 THROUGH 421.5.2.6. SUCH LINERS
 SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES (51
 MM) ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE
 COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH
 SECTION 312.9. NOTE; THRESHOLDS IN ROLL-IN TYPE SHOWER
 COMPARTMENTS SHALL BE 1/2 INCH HIGH MAXIMUM IN
 ACCORDANCE WITH FBC ACC 303.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER