Notes |
Date |
Text |
2021-06-24 10:47:37 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B 107.2.1, THE WINDOW SCHEDULE ON SHEET A-1 | | INDICATES THAT THE FIXED WINDOWS ARE TO BE IMPACT | | RESISTANT, BUT THE SUBMITTED N.O.A. (FIXED WINDOWS) IS | | FOR NON-IMPACT RATED WINDOWS. PLEASE CORRECT PLAN | | SHEETS OR PROVIDE AN N.O.A FOR IMPACT RESISTANT FIXED | | WINDOWS. | | | | 2) FBC B 107.2.1, PLEASE PROVIDE THE ENERGY | | CALCULATIONS. | | | | 3) NOTE: THE VALUATION MAY NEED TO CHANGE, AS CHANGING | | THE SCREENED ENCLOSED PORCH TO A HABITABLE SPACE MUST | | MEET THE ELECTRIC AND MECHANICAL REQUIREMENTS. | | |
|