Plan Review Notes For Permit 21060357 |
Permit Number |
21060357 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-06-30 10:44:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | FEEDER NOT SUPPLYING ENTIRE LOAD PLEASE CHANGE TO 3/0. | | | | FOR A FEEDER RATED 100 THROUGH 400 AMPERES, THE FEEDER | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING | | THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING | | UNIT IN A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE | | PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT | | OF THE FEEDER RATING. |
|