2021-11-10 14:20:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE PROPOSED STRUCTURE IS CLASSIFIED AS A STORAGE |
| OCCUPANCY PER THE NFPA 101 LIFE SAFETY CODE. |
| |
| THERE ARE 3 DOORS THAT MAY SERVE AND FUNCTION AS THE |
| REQUIRED EXIT. |
| |
| PER NFPA 101 CH 42 STORAGE OCCUPANCIES |
| |
| 42.1.1.5 STORAGE OCCUPANCIES SHALL INCLUDE ALL |
| BUILDINGS OR STRUCTURES |
| USED PRIMARILY FOR THE STORAGE OR SHELTERING OF GOODS, |
| MERCHANDISE, |
| PRODUCTS, OR VEHICLES. |
| |
| 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| SHALL HAVE |
| SIGNS IN ACCORDANCE WITH SECTION 7.10. |
| |
| 7.10.1.2 EXITS. |
| 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| THAT OBVIOUSLY |
| AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| BY AN APPROVED |
| SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| ACCESS. |
| |
| PLEASE INDICATE WHICH DOOR IS THE REQUIRED EXIT AND |
| MARK IT ACCORDINGLY WITH AN EXIT SIGN. |
| |
| |
| 2) THE LOCKS ON THE REQUIRED EXIT DOOR SHALL COMPLY |
| WITH NFPA 101 |
| |
| 42.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| |
| 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| READILY FROM THE |
| EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| |
| 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A TOOL, |
| OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| EGRESS SIDE. |
| |
| PLEASE PROVIDE THE REQUIRED EXIT DOOR WITH A COMPLIANT |
| LOCK IF INSTALLED. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |