Plan Review Notes For Permit 21060282 |
Permit Number |
21060282 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-10-18 14:32:59 | THE PREVIOUS COMMENTS FROM FIRE HAVE NOT BEEN | | SPECIFICALLY ADDRESSED. | | | | | | PLEASE PROVIDE A DETAILED RESPONSE | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATION OF WHAT THE INTENDED USE OF | | THE PROPOSED SHED. | | | | PLEASE PROVIDE A DETAILED NARRATIVE OF THE INTENDED | | USE. | | | | | | | | 2) THERE ARE NO INDICATIONS OF AN INTERIOR FLOOR PLAN. | | | | PLEASE PROVIDE A DETAILED INTERIOR FLOOR PLAN. | | | | | | 3) THERE NO INDICATIONS OF ELECTRICAL WIRING OR | | LIGHTING INCLUDING EXIT SIGNS AND EMERGENCY | | LIGHTS(BASED OF THE OCCUPANCY) | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|