Plan Review Notes For Permit 21060251 |
Permit Number |
21060251 |
|
Review Stop |
R |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-10-18 10:17:22 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING (FL16730 | | ) = NEED TO CHOOSE A ROOFING SYSTEM IN THE PRODUCT | | APPROVAL THAT SHOWS THE REQUIRED WIND DESIGN PRESSURE - | | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE ADDITIONAL | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND | | PRESSURE THEN THE CHOSEN ROOFING SYSTEM - SEE NOTES ON | | THE PRODUCT APPROVAL. | | | | | | | | | | |
|