Plan Review Notes
Plan Review Notes For Permit 21060251
Permit Number 21060251
Review Stop P
Sequence Number 3
Notes
Date Text
2021-10-20 12:30:473RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21060251
 10/20/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS- DENIED.
  
 1) THE ITEMS LISTED BELOW WERE SUBMITTED WITHOUT
 APPROVAL STAMPS BY EITHER THE ARCHITECT OR ENGINEER OF
 RECORD:
 A) OIL/SAND INTERCEPTOR
 B) RECLAIM TANKS
 C) WASH EQUIPMENT
 D) VACUUM EQUIPMENT
 E) AIR COMPRESSOR
 PLEASE NOTE THAT THE APPROVAL STAMPS ON THE INTERCEPTOR
 AND RECLAIM TANKS WERE NOT SIGNED BY EITHER THE
 ARCHITECT OR ENGINEER OF RECORD- SECTION 107.3.4 WPB.
 REFER TO SECTIONS 107.1 AND 107.3.4.1: THE ITEMS ABOVE
 MAY BE DEFERRED HOWEVER IT WOULD BE HELPFUL TO PROVIDE
 A MASTER LIST ON THE PLAN OF ALL DEFERRED SUBMITTALS.
  
 2) SUBMITTAL ITEMS LISTED BELOW WERE REQUESTED BUT NOT
 SUBMITTED:
 A) RECLAIM AND OIL/SAND INTERCEPTOR TANK HEAVY DUTY
 TRAFFIC LIDS
 B) WATER HEATER
 C) EXPANSION TANK
 D) RECIRCULATION PUMP
 E) MIXING VALVES
 REFER TO SECTIONS 107.1 AND 107.3.4.1: THE ITEMS ABOVE
 MAY BE DEFERRED HOWEVER IT WOULD BE HELPFUL TO PROVIDE
 A MASTER LIST ON THE PLAN OF ALL DEFERRED SUBMITTALS.
  
 3) SHEETS P1.1 & PR7.4: THE PLANS SHOW RECLAIM TANKS
 WITH TWO MANHOLE OPENINGS HOWEVER THE SHOP DRAWINGS
 SHOW TANKS WITH TWO OPENINGS. WHICH ARE THE TANKS TO BE
 INSTALLED?
  
 4) PR7.4: AS NOTED IN COMMENT #2, HEAVY DUTY TANK LID
 COVERS WERE NOT SUBMITTED. PLEASE NOTE THE LIDS SHALL
 BE HS-20 AASHTO RATED. THE LIDS MAY BE DEFERRED AND
 ADDED TO THE MASTER LIST.
  
 5) BASED ON THE SUBMITTED SHOP DRAWINGS, THE VACUUM
 SYSTEM REQUIRES STRUCTURAL ENGINEERING FOR INSTALLATION
 HOWEVER THE ENGINEERING HAS NOT BEEN PROVIDED. PLEASE
 PROVIDE THE ENGINEERING OR INDICATE IT WILL BE
 DEFERRED- SECTION 107.3.4.1 WPB. PLEASE NOTE THAT THE
 STRUCTURAL ENGINEERING SHALL INCLUDE WIND LOAD
 ENGINEERING FOR TIE DOWN OF EXPOSED EQUIPMENT- SECTION
 301.15 FBC M.
  
 6) P5.1: PLEASE CORRECT THE NOTE INDICATING 110-DEGREE
 HOT WATER SUPPLY TO THE LAVATORIES FROM THE MIXING
 VALVE- SEE DEFINITIONS OF HOT AND TEMPERED WATER.
 TEMPERED WATER IS REQUIRED AT THE LAVS AND IS DEFINED
 AS WATER WITH TEMPERATURE BETWEEN 85-110 DEGREES F. HOT
 WATER IS EQUAL TO OR GREATER THAT 110.
  
 7) P2.1 & PR7.2: THE MAN POTABLE WATER SERVICE BACKFLOW
 PREVENTER IS INDICATED AS BF-1 ON P2.1 & BF-2 ON PR7.2.
 PLEASE SEE TABLE 608.1 FBC P AND PROVIDE A BACK FLOW
 PREVENTER RATED FOR HIGH HAZARD.
  
 8) P3.1: PLEASE PROVIDE THE GPM DRAINAGE FLOW FOR EACH
 ZONE OR AT EACH RD SHOWN IN THE ISO- TABLE 1106.3 FBC
 P.
  
 9) A8.1: THE SCUPPER DETAIL DOES NOT APPEAR IN
 COMPLIANCE WITH SECTION 1503.4..2.1 FBC B WHICH
 INDICATES THE SCUPPERS SHALL BE PLACED IN THE PARAPET
 WALLS NOT LESS THAN 2 INCHES NOR MORE THAN 4 INCHES
 ABOVE THE ROOF COVERING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  