Date |
Text |
2021-10-20 12:30:47 | 3RD REVIEW FBC-2020 PLUMBING |
| PERMIT- 21060251 |
| 10/20/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS- DENIED. |
| |
| 1) THE ITEMS LISTED BELOW WERE SUBMITTED WITHOUT |
| APPROVAL STAMPS BY EITHER THE ARCHITECT OR ENGINEER OF |
| RECORD: |
| A) OIL/SAND INTERCEPTOR |
| B) RECLAIM TANKS |
| C) WASH EQUIPMENT |
| D) VACUUM EQUIPMENT |
| E) AIR COMPRESSOR |
| PLEASE NOTE THAT THE APPROVAL STAMPS ON THE INTERCEPTOR |
| AND RECLAIM TANKS WERE NOT SIGNED BY EITHER THE |
| ARCHITECT OR ENGINEER OF RECORD- SECTION 107.3.4 WPB. |
| REFER TO SECTIONS 107.1 AND 107.3.4.1: THE ITEMS ABOVE |
| MAY BE DEFERRED HOWEVER IT WOULD BE HELPFUL TO PROVIDE |
| A MASTER LIST ON THE PLAN OF ALL DEFERRED SUBMITTALS. |
| |
| 2) SUBMITTAL ITEMS LISTED BELOW WERE REQUESTED BUT NOT |
| SUBMITTED: |
| A) RECLAIM AND OIL/SAND INTERCEPTOR TANK HEAVY DUTY |
| TRAFFIC LIDS |
| B) WATER HEATER |
| C) EXPANSION TANK |
| D) RECIRCULATION PUMP |
| E) MIXING VALVES |
| REFER TO SECTIONS 107.1 AND 107.3.4.1: THE ITEMS ABOVE |
| MAY BE DEFERRED HOWEVER IT WOULD BE HELPFUL TO PROVIDE |
| A MASTER LIST ON THE PLAN OF ALL DEFERRED SUBMITTALS. |
| |
| 3) SHEETS P1.1 & PR7.4: THE PLANS SHOW RECLAIM TANKS |
| WITH TWO MANHOLE OPENINGS HOWEVER THE SHOP DRAWINGS |
| SHOW TANKS WITH TWO OPENINGS. WHICH ARE THE TANKS TO BE |
| INSTALLED? |
| |
| 4) PR7.4: AS NOTED IN COMMENT #2, HEAVY DUTY TANK LID |
| COVERS WERE NOT SUBMITTED. PLEASE NOTE THE LIDS SHALL |
| BE HS-20 AASHTO RATED. THE LIDS MAY BE DEFERRED AND |
| ADDED TO THE MASTER LIST. |
| |
| 5) BASED ON THE SUBMITTED SHOP DRAWINGS, THE VACUUM |
| SYSTEM REQUIRES STRUCTURAL ENGINEERING FOR INSTALLATION |
| HOWEVER THE ENGINEERING HAS NOT BEEN PROVIDED. PLEASE |
| PROVIDE THE ENGINEERING OR INDICATE IT WILL BE |
| DEFERRED- SECTION 107.3.4.1 WPB. PLEASE NOTE THAT THE |
| STRUCTURAL ENGINEERING SHALL INCLUDE WIND LOAD |
| ENGINEERING FOR TIE DOWN OF EXPOSED EQUIPMENT- SECTION |
| 301.15 FBC M. |
| |
| 6) P5.1: PLEASE CORRECT THE NOTE INDICATING 110-DEGREE |
| HOT WATER SUPPLY TO THE LAVATORIES FROM THE MIXING |
| VALVE- SEE DEFINITIONS OF HOT AND TEMPERED WATER. |
| TEMPERED WATER IS REQUIRED AT THE LAVS AND IS DEFINED |
| AS WATER WITH TEMPERATURE BETWEEN 85-110 DEGREES F. HOT |
| WATER IS EQUAL TO OR GREATER THAT 110. |
| |
| 7) P2.1 & PR7.2: THE MAN POTABLE WATER SERVICE BACKFLOW |
| PREVENTER IS INDICATED AS BF-1 ON P2.1 & BF-2 ON PR7.2. |
| PLEASE SEE TABLE 608.1 FBC P AND PROVIDE A BACK FLOW |
| PREVENTER RATED FOR HIGH HAZARD. |
| |
| 8) P3.1: PLEASE PROVIDE THE GPM DRAINAGE FLOW FOR EACH |
| ZONE OR AT EACH RD SHOWN IN THE ISO- TABLE 1106.3 FBC |
| P. |
| |
| 9) A8.1: THE SCUPPER DETAIL DOES NOT APPEAR IN |
| COMPLIANCE WITH SECTION 1503.4..2.1 FBC B WHICH |
| INDICATES THE SCUPPERS SHALL BE PLACED IN THE PARAPET |
| WALLS NOT LESS THAN 2 INCHES NOR MORE THAN 4 INCHES |
| ABOVE THE ROOF COVERING. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |