2021-09-09 14:53:25 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED. |
| |
| A-NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CONDENSATE |
| DRAIN FOR AHU-1. PLEASE NOTE, PER WPB CODE OF ORDINANCE |
| CHAPTER 90, ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE |
| SHALL NOT DISCHARGE TO THE CITY UTILITIES SANITARY |
| SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM THE |
| UTILITIES DEPARTMENT. YOU MAY CONTACT MR. MANNY |
| GONZALES IN ENGINEERING AT 561-494-1128 FOR ADDITIONAL |
| INFORMATION. MOVING FORWARD, DISCHARGE THE CONDENSATE |
| TO AN EXTERIOR DRYWELL OR STORM SYSTEM; PER WPB FBC |
| 107.2.1, PROVIDE ROUTING, TERMINATION AND A |
| DRYWELL/STORM CONNECTION DETAIL. |
| |
| |
| 1) A1.0, A2.2, P1.1: PROVIDE PLUMBING FIXTURE |
| CALCULATIONS IN ACCORDANCE WITH TABLE 403.1. |
| SECOND REQUEST: PROVIDE A SCHEDULE THAT INDICATES THE |
| REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES FOR A |
| BUSINESS OCCUPANCY. |
| |
| 2) COMPLIED |
| |
| 3) |
| ...A) COMPLIED |
| ...B) SECOND REQUEST: PROVIDE AN EQUIPMENT SCHEDULE FOR |
| THE INTERCEPTOR ON THE PLAN |
| ...C) SECOND REQUEST: PROVIDE SIZING CALCULATIONS PER |
| THE MANUFACTURER IN ACCORDANCE WITH SECTION 1003.4.2.2- |
| NOT LESS THAN 6 CU. FT. FOR THE FIRST 100 SQ. FT. OF |
| AREA TO BE DRAINED PLUS 1 CU. FT. FOR EACH ADDITIONAL |
| 100 SQ. FT. |
| ...D) NEW COMMENT: P1.1, P4.0; SHOW UPSTREAM AND |
| DOWNSTREAM CLEANOUTS ON ALL RECLAIM TANKS |
| ...E) SECOND REQUEST: PLEASE SUBMIT SPECS FOR THE LIDS. |
| F) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- SECTION |
| 107.2.1, 107.3.4. WPB. SUBMITTALS MAY BE DEFERRED IN |
| ACCORDANCE WITH SECTION 107.3.4.1 WPB. |
| |
| 4) |
| ...A) COMPLIED |
| ...B) SECOND REQUEST: PROVIDE EQUIPMENT SCHEDULES ON |
| THE PLANS FOR THE TANKS |
| ...C) SECOND REQUEST: INDICATE HOW THE TANKS WERE SIZED |
| AND PROVIDE CALCULATIONS. |
| ...D) COMPLIED |
| ...E) SECOND REQUEST: HEAVY DUTY TRAFFIC LIDS ARE |
| REQUIRED FOR TANK ACCESS OPENINGS- SECTIONS 305.7 & |
| 1309.6. PLEASE SUBMIT SPECS FOR THE LIDS. F) ALL |
| SUBMITTALS SHALL BE APPROVED AND STAMP BY THE DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE- SECTIONS 107.2.1 & |
| 107.3.4. WPB. SUBMITTALS MAY BE DEFERRED IN ACCORDANCE |
| WITH SECTION 107.3.4.1 WPB. |
| |
| 5) COMPLIED: CAR WASH SYSTEM |
| NEW COMMENT: PROVIDE INTER-CONNECTION AND BACKFLOW |
| PREVENTER BETWEEN DOMESTIC WATER SYSTEM AND WASH |
| SYSTEM. SEE COMMENT 16 REGARDING INTER-CONNECTION |
| BETWEEN DOMESTIC WATER AND WASH SYSTEM. |
| |
| 6) VACUUM SYSTEM- SECTION 107.2.1 WPB: |
| ...A) COMPLIED |
| ...B) COMPLIED |
| SECOND REQUEST: BY REVIEWING THE MANUFACTURER?S |
| SPECIFICATIONS/MANUAL, IT APPEARS PIPING MATERIAL IS |
| PVC PIPE WITH SOLVENT WELD FITTINGS BUT IS MANUFACTURER |
| SPECIFIC FOR THE SYSTEM, WOULD BE FURNISHED IN THE |
| ACTUAL BOM AND IS NOT COMPATIBLE WITH STANDARD DRAINAGE |
| OR WATER USE PVC MATERIAL AS IS FOUND IN FBC PL |
| CHAPTERS 6 AND 7. IS THIS THE CASE? PLEASE PROVIDE |
| MANUFACTURER?S SPECIFICATION FOR THIS MATERIAL. |
| |
| 7) COMPLIED |
| |
| 8) A4.0- MISSING DETAILS PER FBC ACC: |
| ...A) COMPLIED |
| ...B) COMPLIED |
| ...C) COMPLIED |
| ...D) SECOND REQUEST: SHOW THE HEIGHT OF THE MIRROR |
| FROM THE FINISHED FLOOR TO THE REFLECTIVE SURFACES (NOT |
| THE BOTTOM OF THE MIRROR) SECTION 603.3 |
| ...E) SECOND REQUEST: SHOW THE HEIGHTS OF THE GRAB BARS |
| FOR THE FINISHED FLOORS TO THE TOPS NOT THE CENTER OF |
| THE GRIPPING SURFACES- SECTION 609.4. |
| ...F) COMPLIED |
| ...G)SECOND REQUEST: SHOW KNEE AND TOE CLEARANCES FOR |
| THE LAVATORIES- SECTION 606.2 & FIGURES 306.2 & 306.3. |
| ...H) N/A |
| NEW COMMENT: PER WPB FBC 107.2.1, REMOVE |
| REFERENCES/DETAILS REGARDING DRINKING FOUNTAIN FROM |
| A4.0, AS THERE IS NO DRINKING FOUNTAIN. |
| |
| 9) COMPLIED. |
| |
| 10) P1.1: PROVIDE THE PIPE SLOPES- TABLE 704.1 FBC P. |
| NEW COMMENT:TABLE 704.1 REQUIRES PIPING SMALLER THAN 3 |
| INCH SHALL HAVE A MINIMUM SLOPE OF 1/4 INCH PER FOOT. |
| PIPING 3 INCH TO 6 INCH MINIMUM SLOPE TO BE 1/8 INCH |
| PER FOOT. SEE P4.1 AND REVISE NOTE TO REFLECT PER WPB |
| FBC 107.2.1. |
| |
| 11) COMPLIED:P1.1 & P4.1: THE PLANS SHOW ONLY ONE OF |
| THE TWO DRAIN LINES FROM THE TUNNEL PITS DISCHARGING |
| INTO THE OIL/WATER SEPARATOR- SECTION 1003.4.2 FBC P. |
| NEW COMMENT: PER FBC PL 1003.2, THE SERVICE SINK SHALL |
| NOT DISCHARGE INTO THE OIL SEPARATOR. |
| NEW COMMENT: PIT SYSTEM 2 AND TRENCH DRAIN SYSTEM |
| DISCHARGE DIRECTLY TO THE OIL WATER SEPARATOR. SOME |
| TRENCH DRAINS ARE TRAPPED. PIT AND ONE OTHER TRENCH |
| DRAIN ARE NOT. PER WPB FBC 107.2.1, CLARIFY. |
| |
| 12) COMPLIED |
| |
| 13) COMPLIED |
| |
| 14) COMPLIED |
| |
| 15) SECOND REQUEST: INDICATE THE EFFICIENCY RATING OF |
| THE UNIT PER TABLE C404.1 FBC EC AND SUBMIT |
| MANUFACTURERS SPECIFICATIONS AND INSTALLATION MANUAL- |
| SECTION 502.1. |
| NEW COMMENT(S) |
| ...A) THERMAL EXPANSION TANK SHALL BE CONNECTED TO THE |
| WATER HEATER COLD WATER SUPPLY PIPE, NOT THE HOT WATER |
| AT A POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES, |
| PRESSURE REDUCING VALVES AND BACKFLOW PREVENTERS PER |
| FBC PL 607.3. PER WPB FBC 107.2.1, SHOW THE THERMAL |
| EXPANSION TANK ON THE PROVIDED WATER HEATER DETAIL AS |
| WELL AS ON THE ISOMETRIC. |
| ...B) PER WPB FBC 107.2.1, SPECIFY AND SIZE THE THERMAL |
| EXPANSION TANK; SHALL BE SIZED IN ACCORDANCE WITH THE |
| MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH |
| THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM |
| SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8. FBC PL |
| 607.3 |
| ...C) PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND |
| DETAIL FOR RECIRCULATION PUMP. SHOW HOW HOT WATER |
| RETURN WILL INTRODUCED INTO THE WATER HEATER, EITHER |
| DIRECTLY OR THROUGH THE COLD WATER SUPPLY. INCLUDE ALL |
| BALANCING VALVES, SHUT OFF VALVES, CHECK VALVES AND |
| CONTROLS. |
| |
| 16) SECOND REQUEST: P2.1, P5.1, PR7.2: PROVIDE THE TYPE |
| OF BACKFLOW PREVENTER TO BE INSTALLED AT THE WATER |
| DISTRIBUTION ENTRANCE TO THE EQUIPMENT ROOM- SECTION |
| 608.3 FBC P. |
| REVISE SHEETS P2.1 & P5.1 TO SHOW THE EXACT LOCATION OF |
| THE POTABLE WATER LINE CONNECTION TO THE WASH EQUIPMENT |
| AS SHOWN ON PR7.2. PROVIDE A BACKFLOW PREVENTER |
| ASSEMBLY AT THIS LOCATION AND INDICATE THE TYPE- |
| SECTION 608.3. THIS SYSTEM SHALL BE COMPLETELY ISOLATED |
| FOR THE POTABLE WATER SUPPLY AND THE WATER SUPPLY TO |
| THE PLUMBING FIXTURES IN THE EQUIPMENT ROOM. SHEET |
| PR7.2 SHOWS INDIVIDUAL BACKUP POTABLE WATER LINES TO |
| EQUIPMENT. BACKFLOW PREVENTERS WILL BE REQUIRED ON EACH |
| LINE- SECTION 608.3. |
| |
| 17) NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE |
| SPECIFICATION AND DETAIL FOR MIXING VALVE AND HOT WATER |
| CARTRIDGE NOTED IN RESPONSE. DEVICE SHALL CONFORM TO |
| ASSE 1070 PER FBC PL 419.5 AND 607.2.1. |
| |
| 18) SECOND REQUEST: P2.1 & P5.1: REFER TO TABLE |
| C404.5.1 FBC EC- THE 1/2 -INCH HOT WATER PIPE TO THE |
| LAVATORY SHALL NOT EXCEED 2FT. FROM THE HOT WATER |
| SOURCE. |
| THE MAXIMUM ALLOWABLE PIPING LENGTH FROM THE NEAREST |
| SOURCE OF HEATED WATER TO THE TERMINATION OF THE |
| FIXTURE SUPPLY PIPE SHALL BE IN ACCORDANCE WITH THE |
| FOLLOWING. WHERE THE PIPING CONTAINS MORE THAN ONE SIZE |
| OF PIPE, THE LARGEST SIZE OF PIPE WITHIN THE PIPING |
| SHALL BE USED FOR DETERMINING THE MAXIMUM ALLOWABLE |
| LENGTH OF THE PIPING IN TABLE C404.5.1. |
| FOR A PUBLIC LAVATORY FAUCET, USE THE ?PUBLIC LAVATORY |
| FAUCETS? COLUMN IN TABLE C404.5.1. |
| PLEASE NOTE THAT THE NEAREST SOURCE OF HEATED WATER IS |
| WHERE THE HOT WATER RETURN CONNECTS TO THE HOT WATER. |
| TABLE C404.5.1 REQUIRES THAT THE 1/2 INCH PIPING FROM |
| THE SOURCE TO THE POINT OF TERMINATION NOT EXCEED 2 |
| FEET. |
| ADDITIONALLY, FOR YOUR INFORMATION NOTE THAT FBC PL |
| 419.5 (2020 7TH EDITION) STATES THAT COLD OR TEMPERED |
| WATER SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH |
| FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED |
| FOR CUSTOMERS, PATRONS AND VISITOR. |
| |
| |
| 19) NEW COMMENT: P5.1, KEY NOTE 1 CALLS FOR FOAM GLASS |
| INSULATION, 1.5 INCHES THICK. P6.1, PLUMBING NOTE 16 |
| CALLS FOR 1 INCH THICK SNAP ON INSULATION. PER WPB FBC |
| 107.2.1, CLARIFY AND RECONCILE HOT WATER INSULATION |
| SPECS ON |
| |
| 20) COMPLIED: SEE ENGINEER/ARCHITECT RESPONSE; INDUSTRY |
| STANDARD; AUTO WASH EQUIPMENT DOES NOT INCORPORATE HOT |
| WATER. |
| |
| 20) COMPLIED |
| |
| 21) P3.1 ROOF DRAINAGE- SECTION 1101 FBC P: |
| ...A) COMPLIED: PROVIDE THE RAINFALL RATE USED FOR THE |
| CALCULATIONS- 1106.1. |
| ...B) SECOND REQUEST: PROVIDE A BREAKDOWN OF THE |
| CALCULATIONS THAT INCLUDES THE PARAPET AREAS- 1106.4. |
| TO BE CLEAR, THE AREA OF THE ROOF AND THE REQUIRED AREA |
| OF THE PARAPET WALLS (HALF THE AREA IS REQUIRED) SHALL |
| BE BROKEN OUT IN THE CALCULATIONS. |
| ...C) COMPLIED: PROVIDE AN ISOMETRIC DRAWING- 1101.2- |
| 1101.8. |
| NEW COMMENT: ADD ISOMETRIC FOR ZONE 4. |
| ...D) VERIFY COMPLIANCE WITH 1107.1 ROOF DESIGN- ROOFS |
| SHALL BE DESIGNED FOR THE MAXIMUM POSSIBLE DEPTH OF |
| WATER THAT WILL POND THEREON AS DETERMINED BY THE |
| RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS, |
| SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION |
| WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING |
| THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF |
| DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE |
| MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL |
| INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE |
| INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE |
| THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS |
| TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY |
| SECTION 1106. |
| NEW COMMENT: PER WPB FBC 107.2.1, PLEASE EDIT ARCHITECT |
| RESPONSE TO COMMENT 21.D TO NOTE SQUARE FOOTAGE |
| INCLUDES HALF THE AREA OF THE PARAPET WALLS AND INSERT |
| ENTIRE COMMENT ONTO P3.1 PLUMBING ROOF PLAN DRAINAGE. |
| ...E) IT APPEARS THE EMERGENCY OVERFLOW SCUPPERS HAVE |
| NOT PLACED IN LOCATIONS THAT WILL ACCOMMODATE ALL AREAS |
| OF THE ROOF- SECTION 1106.5 FBC P, AND 1503.4.1 & |
| 1503.4.2 FBC B. |
| NEW COMMENT: PER WPB FBC 107.2.1, PLEASE INSERT |
| ARCHITECT RESPONSE TO COMMENT 21.E ONTO P3.1 PLUMBING |
| ROOF PLAN DRAINAGE. |
| |
| 22) COMPLIED |
| |
| 23) SECOND REQUEST: NON-POTABLE WATER SIGNAGE IS |
| REQUIRED IN THE EQUIPMENT ROOM, HOSE BIB LOCATIONS, AND |
| AT ALL COMPONENTS OF THE RECLAIMED WATER SYSTEM- |
| SECTIONS 1301.3 & 13091.9.9 FBC P. PLEASE SHOW SIGN |
| LOCATIONS AND PROVIDE SIGNAGE DETAILS. |
| THE ARCHITECT AND MEP RESPONSE TO THIS WAS TO DEFER TO |
| THE OTHER WITH NO RESOLUTION OFFERED. |
| TO BE CLEAR, PER FBC PL 1301.3 STATES NONPOTABLE WATER |
| OUTLETS SUCH AS HOSE CONNECTIONS, OPEN ENDED PIPES AND |
| FAUCETS SHALL BE IDENTIFIED AT THE POINT OF USE FOR |
| EACH OUTLET WITH THE SIGNAGE. IF THERE ARE NO SUCH |
| OUTLETS IN THE RECLAIM SYSTEM, THEN PLEASE NOTE SUCH. |
| IF THERE ARE THEN PLEASE IDENTIFY AND PROVIDE DETAIL |
| FOR PROPER SIGNAGE. SEE 1301.3 |
| FBC PL 1301.9.9 STATES EACH NONPOTABLE WATER STORAGE |
| TANK SHALL BE LABELED WITH ITS RATED CAPACITY. THE |
| CONTENTS OF STORAGE TANKS SHALL BE IDENTIFIED WITH THE |
| WORDS ?CAUTION: NONPOTABLE WATER ? DO NOT DRINK.? WHERE |
| AN OPENING IS PROVIDED THAT COULD ALLOW THE ENTRY OF |
| PERSONNEL, THE OPENING SHALL BE MARKED WITH THE WORDS, |
| ?DANGER ? CONFINED SPACE.? MARKINGS SHALL BE INDELIBLY |
| PRINTED ON THE TANK OR ON A TAG OR SIGN CONSTRUCTED OF |
| CORROSION-RESISTANT WATERPROOF MATERIAL THAT IS MOUNTED |
| ON THE TANK. THE LETTERS OF THE WORDS SHALL BE NOT LESS |
| THAN 0.5 INCH (12.7 MM) IN HEIGHT AND SHALL BE OF A |
| COLOR IN CONTRAST WITH THE BACKGROUND ON WHICH THEY ARE |
| APPLIED. |
| |
| |
| 24) UPDATED SURVEY SUBMITTED; FFE=20.30 NAVD. FLOOD |
| ZONE AE12 AFFECTS ONLY THE NORTHEAST CORNER OF THE |
| BUILDING. ALL ITEMS/INFRASTRUCTURE NOTED BELOW ARE |
| OUTSIDE OF FLOOD ZONE AE12. GEOTECHNICAL REPORTS |
| GROUNDWATER AT 10.4 FEET TO 12.6 FEET BELOW GROUND |
| SURFACE DEPENDING UPON BORING LOCATIONS, FEBRUARY |
| 25-26, 2021 MIDDLE OF THE DRY SEASON; THE SURVEY |
| INDICATES GROUND SURFACE ELEVATIONS IN AREA OF THE |
| TANKS TO RANGE FROM 18.16 FEET TO 18.61 FEET. THE |
| BOTTOM OF THE DEEPEST RECLAIM TANK ACCORDING TO INV. |
| PIPE ELEVATIONS GIVEN ON C7.0 WATER AND SEWER PLAN AND |
| THE SHOP DRAWINGS FOR THE 2000 GAL. GT NEW STOCK (CLAM) |
| MODEL- SHOP DRAWING- OLDCASTLE IS AT OR NEAR 8 FEET |
| BELOW THE EXISTING GROUND SURFACE. THE BOTTOM OF THE |
| OIL/WATER SEPARATOR ACCORDING TO INV. PIPE ELEVATIONS |
| GIVEN ON C7.0 WATER AND SEWER PLAN AND THE SHOP |
| DRAWINGS FOR THE OIL SAND SEPARATOR- SHOP DRAWING B2B |
| IS AT OR NEAR 7 FEET BELOW THE EXISTING GROUND SURFACE. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |