2021-09-16 12:58:50 | NEW COMMERCIAL BUILDING |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| 1) DRAWING A1.0 STATES THAT THE BUILDING IS IN A FLOOD |
| ZONE "X" - SURVEY PROVIDED SHOWS THE BUILDING IN A |
| FLOOD ZONE (AE12.70) AND (X) - PLEASE REVISE THE |
| DRAWING. |
| |
| 2) PLEASE SHOW THE "LOWEST FLOOR" ELEVATION USING |
| "NAVD" ON THE DRAWINGS FBC 1612.1 |
| |
| 3) PLEASE SHOW THE ACCESSIBLE RESTROOM MIRROR |
| DIMENSIONS FROM THE FINISHED FLOOR TO THE "REFLECTING |
| SURFACE" TO COMPLY WITH FBC 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 4) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE EXTERIOR DOORS - REVIEWED AND |
| MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD FBC |
| WPB 107.3.4 |
| |
| 5) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING (FL16730 |
| ) = NEED TO CHOOSE A ROOFING SYSTEM IN THE PRODUCT |
| APPROVAL THAT SHOWS THE REQUIRED WIND DESIGN PRESSURE - |
| PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE |
| PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE ADDITIONAL |
| ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR |
| THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND |
| PRESSURE THEN THE CHOSEN ROOFING SYSTEM - SEE NOTES ON |
| THE PRODUCT APPROVAL. |
| |
| 6) PLEASE PROVIDE THE FRONT PAGES FOR THE FLORIDA STATE |
| OR MIAMI DADE PRODUCT APPROVALS - THE ONLY FRONT PAGE |
| PROVIDED IS FOR THE LOUVERS - PLEASE PROVIDE THE FRONT |
| PAGES FOR ALL OTHER PRODUCT APPROVALS. |
| |
| |
| |