2021-08-06 09:45:54 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21060251 |
| 8/5/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A1.0, A2.2, P1.1: PROVIDE PLUMBING FIXTURE |
| CALCULATIONS IN ACCORDANCE WITH TABLE 403.1. PROVIDE A |
| SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED |
| NUMBER OF PLUMBING FIXTURES FOR A BUSINESS OCCUPANCY. |
| THE CALCULATIONS SHALL INCLUDE THE OCCUPANT LOADS OF |
| ALL AREAS OUTSIDE OF THE BUILDING THAT ARE USED AS PART |
| OF THE BUILDING?S DESIGNATED OCCUPANCY INCLUDING THE |
| VACUUM AREA- SECTION 403.1.4 FBC P. PLEASE NOTE THAT |
| PLUMBING FIXTURES SHALL BE PROVIDED FOR PATRONS AND |
| EMPLOYEES OF THE BUSINESS. EMPLOYEE TOILET FACILITIES |
| SHALL BE SEPARATE OR COMBINED EMPLOYEE AND PUBLIC |
| FACILITIES- SECTION 403.3 FBC P. PLEASE INCLUDE THE |
| NUMBER OF PATRONS AND EMPLOYEES IN THE CALCULATIONS. |
| REVIEW THE FOLLOWING APPLICABLE CODE SECTIONS: |
| |
| A) TABLE 403.1 REQUIRES DRINKING FOUNTAINS AND A |
| SERVICE SINK FOR B OCCUPANCIES WHICH DO NOT APPEAR TO |
| BE SHOWN ON THE PLUMBING PLANS. |
| |
| B) SEPARATE PLUMBING FIXTURES AND FACILITIES SHALL BE |
| PROVIDED FOR EACH SEX UNLESS THE MAXIMUM OCCUPANT LOAD |
| IS 25 OR FEWER- SECTION 403.2 (4) FBC P. |
| |
| 2) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| THE POTABLE WATER SERVICE BACKFLOW PREVENTER, |
| IRRIGATION SYSTEM, AND OIL/WATER SEPARATOR- SECTIONS |
| 105.1 & 107.2.1 WPB. |
| |
| 3) OIL/WATER SEPARATOR: A SEPARATE PERMIT IS REQUIRED |
| HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN PERMIT IS |
| ALSO REQUIRED. A) PROVIDE AN ENLARGED PIPING DIAGRAM |
| SHOWING THE LOCATIONS OF CLEANOUTS AND VENTS AS |
| REQUIRED BY THE MANUFACTURER AND SECTION 1003.9. B) |
| PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR ON |
| THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS THAT |
| INDICATE THE LISTING AND LABELING OF THE UNIT- SECTION |
| 1003.4.2 FBC P. C) PROVIDE SIZING CALCULATIONS PER THE |
| MANUFACTURER IN ACCORDANCE WITH SECTION 1003.4.2.2- NOT |
| LESS THAN 6 CU. FT. FOR THE FIRST 100 SQ. FT. OF AREA |
| TO BE DRAINED PLUS 1 CU. FT. FOR EACH ADDITIONAL 100 |
| SQ. FT. D) PROVIDE A SITE SPECIFIC, DIMENSIONED |
| INSTALLATION DIAGRAM SHOWING THE BURIAL DEPTH AND INLET |
| AND OUTLET LOCATIONS, CLEAN OUT AND SAMPLING PORT |
| LOCATIONS AND SIZES. PLEASE NOTE A SAMPLING PORT |
| CONSISTING OF A 4-INCH TWO-WAY CLEANOUT TO BE USED AS A |
| SAMPLING PORT MAY BE REQUIRED. PLEASE CONTACT THE CITY |
| OF WEST PALM BEACH UTILITIES DEPT. FOR ADDITIONAL |
| REQUIRED INSPECTION AND TEST SAMPLING INFORMATION AND |
| GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065 |
| OR 561-822-2274 OR EMAIL [email protected]. E) HEAVY DUTY |
| TRAFFIC LIDS ARE REQUIRED FOR TANK ACCESS OPENINGS- |
| SECTIONS 305.7 & 1003.10.PLEASE SUBMIT SPECS FOR THE |
| LIDS. F) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY |
| THE DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- SECTION |
| 107.2.1, 107.3.4. WPB. SUBMITTALS MAY BE DEFERRED IN |
| ACCORDANCE WITH SECTION 107.3.4.1 WPB. |
| |
| 4) RECLAIMED WATER SYSTEM- SECTION 107.2.1 WPB AND |
| 1301.1 & 1304.3 FBC P: A) PROVIDE A COMPLETE PIPING |
| DIAGRAM THAT SHOWS THE PIPE RUNS FROM THE TANKS TO THE |
| EQUIPMENT ROOM AND TO THE CONVEYOR. INCLUDE THE |
| LOCATIONS OF TANK CLEANOUTS, VENTS AND OTHER |
| APPURTENANCES WHERE REQUIRED BY MANUFACTURER'S |
| SPECIFICATIONS. B) PROVIDE EQUIPMENT SCHEDULES ON THE |
| PLANS FOR THE TANKS, AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE TANKS, THE RECLAIM UNIT, AND THE |
| PIPING- SECTIONS 1301.9.2, & 1304.3- 1304.1.3. C) |
| INDICATE HOW THE TANKS WERE SIZED AND PROVIDE |
| CALCULATIONS. D) PROVIDE SITE SPECIFIC, DIMENSIONED |
| TANK AND TANK INSTALLATION DIAGRAMS SHOWING ALL |
| COMPONENTS IF THE TANKS AND BURIAL DEPTHS, WATER INLET |
| AND OUTLET LOCATIONS ETC.- SECTIONS 1309.3- 1309.7. E) |
| HEAVY DUTY TRAFFIC LIDS ARE REQUIRED FOR TANK ACCESS |
| OPENINGS- SECTIONS 305.7 & 1309.6. PLEASE SUBMIT SPECS |
| FOR THE LIDS. F) ALL SUBMITTALS SHALL BE APPROVED AND |
| STAMP BY THE DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- |
| SECTIONS 107.2.1 & 107.3.4. WPB. SUBMITTALS MAY BE |
| DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. |
| |
| 5) CAR WASH SYSTEM: SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR ALL EQUIPMENT LISTED ON SHEET PR7.1 |
| IN THE EQUIPMENT ROOM AND TUNNEL. PLEASE SUBMIT SHOP |
| DRAWINGS FOR THE TUNNEL EQUIPMENT INSTALLATIONS- |
| SECTIONS 107.2.1 AND 107.3.4 WPB. SUBMITTALS MAY BE |
| DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. A) |
| PROVIDE A COMPLETE WATER PIPING DIAGRAM OR RISER |
| DRAWING FOR THE EQUIPMENT ROOM AND WASH TUNNEL. SHOW |
| LOCATIONS OF POTABLE WATER CONNECTIONS, BACKFLOW |
| PREVENTERS, VALVES, AND SHUTOFFS FOR WASH EQUIPMENT- |
| SECTION 107.2.1 & 107.3.5.1.3 WPB. |
| |
| 6) VACUUM SYSTEM- SECTION 107.2.1 WPB: A) SUBMIT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALL MANUALS FOR |
| ALL EQUIPMENT AND PIPING. B) PROVIDE A PIPING LAYOUT |
| PLAN THAT SHOWS THE TYPE OF PIPING, PIPE SIZES, AND |
| PIPING RUNS FROM THE VACUUM ENCLOSURE TO THE STATIONS. |
| |
| 7) AIR COMPRESSOR- SECTION 107.2.1 WPB: A) SUBMIT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALL MANUALS FOR |
| ALL EQUIPMENT AND PIPING. B) PROVIDE A PIPING LAYOUT |
| PLAN THAT SHOWS THE TYPE OF PIPING, PIPE SIZES, AND |
| PIPING RUNS FROM THE COMPRESSOR TO THE EQUIPMENT. |
| |
| 8) A4.0- MISSING DETAILS PER FBC ACC: |
| |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| WATER CLOSET- SECTION 604.3. |
| |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| LAVATORY- SECTION 606.2. ADVISORY: PLEASE NOTE THAT |
| DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACES |
| REQUIRED FOR ACCESSIBLE BATHROOM FIXTURES- SECTION |
| 603.2.3 EXCEPTION 2. |
| |
| C) TURNING SPACE DIAMETER- SECTION 304.3. |
| |
| D) SHOW THE HEIGHT OF THE MIRROR FROM THE FINISHED |
| FLOOR TO THE REFLECTIVE SURFACES SECTION 603.3 |
| |
| E) SHOW THE HEIGHTS OF THE GRAB BARS FOR THE FINISHED |
| FLOORS TO THE TOPS OF THE GRIPPING SURFACES- SECTION |
| 609.4. |
| |
| F) SHOW THE DIMENSIONS FOR THE TOILET REAR GRAB BAR |
| FROM THE CENTER OF THE TOILET PER FBC 604.5.2 REAR |
| WALL. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 |
| MM) LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE |
| WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND |
| 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| |
| G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| 606.2 & FIGURES 306.2 & 306.3. |
| |
| H) SHOW THE LOCATIONS OF THE DRINKING FOUNTAINS AND |
| INDICATE COMPLIANCE WITH SECTION 307.2 PROTRUSION |
| LIMITS. |
| |
| 9) P1.1: PROVIDE A LINE SYMBOL FOR THE RECLAIMED WATER |
| PIPING AND SHOW THE PIPE RUNS INTO THE EQUIPMENT ROOM- |
| SECTION 107.2.1 WPB. |
| |
| 10) P1.1: PROVIDE THE PIPE SLOPES- TABLE 704.1 FBC P. |
| |
| 11) P1.1 & P4.1: THE PLANS SHOW ONLY ONE OF THE TWO |
| DRAIN LINES FROM THE TUNNEL PITS DISCHARGING INTO THE |
| OIL/WATER SEPARATOR- SECTION 1003.4.2 FBC P. |
| |
| 12) P1.1 & P4.1: SHOW THE PIPING RUN FROM THE TRENCH |
| DRAIN BY THE TUNNEL EXIT. PROVIDE A SYMBOL TO IDENTIFY |
| THE TYPE OF PIPING- SANITARY, STORM, OR RECLAIMED- |
| SECTION 107.2.1 WPB. |
| |
| 13) P1.1 & P4.1: A MINIMUM OF ONE VENT THROUGH THE ROOF |
| SHALL BE PROVIDED FOR THE EQUIPMENT TRENCH DRAIN/PIT |
| DRAIN SYSTEM- SECTION 904.1 FBC P. REFER TO SECTION |
| 915.2.5 THE FIXTURE BRANCH OR FIXTURE DRAIN SHALL |
| CONNECT TO THE COMBINATION WASTE AND VENT WITHIN A |
| DISTANCE SPECIFIED IN TABLE 909.1- NOT TO EXCEED 12 FT |
| FOR A 3-INCH DRAIN. |
| |
| 14) P1.1 & P4.1: REVISIONS TO THE PLAN BASED ON COMMENT |
| #1 WILL REQUIRED REVISED DRAINAGE SYSTEM DRAWINGS- |
| SECTIONS 107.2.1 & 107.3.5.1.3 WPB. |
| |
| 15) P2.1, P5.1 & P6.1 WATER HEATER: PLEASE SHOW THE |
| LOCATIONS OF THE THERMAL EXPANSION TANK, RECIRCULATION |
| PUMP, CHECK VALVES, DRAIN PAN, PAN DRAIN LINE RUN AND |
| DISCHARGE LOCATION- SECTIONS 502, 607.2 & 607.3 FBC P. |
| INDICATE THE EFFICIENCY RATING OF THE UNIT PER TABLE |
| C404.1 FBC EC AND SUBMIT MANUFACTURERS SPECIFICATIONS |
| AND INSTALLATION MANUAL- SECTION 502.1. |
| |
| 16) P2.1, P5.1, PR7.2: PROVIDE THE TYPE OF BACKFLOW |
| PREVENTER TO BE INSTALLED AT THE WATER DISTRIBUTION |
| ENTRANCE TO THE EQUIPMENT ROOM- SECTION 608.3 FBC P. |
| REVISE SHEETS P2.1 & P5.1 TO SHOW THE EXACT LOCATION OF |
| THE POTABLE WATER LINE CONNECTION TO THE WASH EQUIPMENT |
| AS SHOWN ON PR7.2. PROVIDE A BACKFLOW PREVENTER |
| ASSEMBLY AT THIS LOCATION AND INDICATE THE TYPE- |
| SECTION 608.3. THIS SYSTEM SHALL BE COMPLETELY ISOLATED |
| FOR THE POTABLE WATER SUPPLY AND THE WATER SUPPLY TO |
| THE PLUMBING FIXTURES IN THE EQUIPMENT ROOM. SHEET |
| PR7.2 SHOWS INDIVIDUAL BACKUP POTABLE WATER LINES TO |
| EQUIPMENT. BACKFLOW PREVENTERS WILL BE REQUIRED ON EACH |
| LINE- SECTION 608.3. |
| |
| 17) P2.1, P5.1: HOT WATER IS BEING SUPPLIED TO THE |
| PUBLIC LAVATORY. PLEASE REFER TO SECTIONS 419.5 AND |
| 607.1.2 AND INDICATE HOW TEMPERED WATER WILL BE |
| SUPPLIED TO THE FIXTURE. |
| |
| 18) P2.1 & P5.1: REFER TO TABLE C404.5.1 FBC EC- THE |
| 1/2 -INCH HOT WATER PIPE TO THE LAVATORY SHALL NOT |
| EXCEED 2FT. FROM THE HOT WATER SOURCE. |
| |
| 19) P2.1 & P5.1: INDICATE THE TYPE AND THICKNESS OF HOT |
| WATER PIPE INSULATION- TABLE C403.2.10 FBC EC. |
| |
| 20) P2.1, P5.1 & PR7.2: HOT WATER IS REQUIRED FOR |
| CLEANSING PURPOSES IN ACCORDANCE WITH SECTION 607.1. |
| PLEASE CLARIFY HOW HOT WATER IS BEING SUPPLIED TO THE |
| CAR WASH SYSTEM. |
| |
| 20) PR7.2: PLEASE PROVIDE PLUMBING KEY LINE SYMBOLS TO |
| IDENTIFY THE PIPING IN THE ROOM- SECTION 107.2.1 WPB. |
| |
| 21) P3.1 ROOF DRAINAGE- SECTION 1101 FBC P: |
| |
| A) PROVIDE THE RAINFALL RATE USED FOR THE CALCULATIONS- |
| 1106.1. |
| |
| B) PROVIDE A BREAKDOWN OF THE CALCULATIONS THAT |
| INCLUDES THE PARAPET AREAS- 1106.4. |
| |
| C) PROVIDE AN ISOMETRIC DRAWING- 1101.2- 1101.8. |
| |
| D) VERIFY COMPLIANCE WITH 1107.1 ROOF DESIGN- ROOFS |
| SHALL BE DESIGNED FOR THE MAXIMUM POSSIBLE DEPTH OF |
| WATER THAT WILL POND THEREON AS DETERMINED BY THE |
| RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS, |
| SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION |
| WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING |
| THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF |
| DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE |
| MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL |
| INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE |
| INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE |
| THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS |
| TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY |
| SECTION 1106. |
| |
| E) IT APPEARS THE EMERGENCY OVERFLOW SCUPPERS HAVE NOT |
| PLACED IN LOCATIONS THAT WILL ACCOMMODATE ALL AREAS OF |
| THE ROOF- SECTION 1106.5 FBC P, AND 1503.4.1 & 1503.4.2 |
| FBC B. |
| |
| 22) NUMEROUS REFERENCES TO CIVIL DRAWINGS HAVE BEEN |
| MADE ON THE PLUMBING PLANS FOR PIPE CONTINUATIONS. |
| PLEASE PROVIDE THE APPLICABLE WATER, SEWER, AND STORM |
| DRAINAGE CIVIL PLANS FOR REVIEW- SECTION 107.2.1 WPB. |
| |
| 23) NON-POTABLE WATER SIGNAGHE IS REQUIRED IN THE |
| EQUIPMENT ROOM, HOSE BIB LOCATIONS, AND AT ALL |
| COMPONENTS OF THE RECLAIMED WATER SYSTEM- SECTIONS |
| 1301.3 & 13091.9.9 FBC P. PLEASE SHOW SIGN LOCATIONS |
| AND PROVIDE SIGNAGE DETAILS. |
| |
| 24) PLEASE NOTE THAT THE BUILDING PLANS EXAMINER HAS |
| DETERMINED THAT THE PROPOSED BUILDING IS A FLOOD ZONE |
| AE12. PLEASE REFER TO SECTION 309.2 FBC P- FOR |
| STRUCTURES LOCATED IN FLOOD HAZARD AREAS, THE FOLLOWING |
| SYSTEMS AND EQUIPMENT SHALL BE LOCATED AND INSTALLED AS |
| REQUIRED BY SECTION 1612 OF THE FLORIDA BUILDING CODE, |
| BUILDING. PLEASE REFER TO SECTION 1301.9.3.1 FOR |
| RECLAIMED WATER TANK BALLASTING REQUIREMENT. |
| 1. WATER SERVICE PIPES. |
| 2. PUMP SEALS IN INDIVIDUAL WATER SUPPLY SYSTEMS WHERE |
| THE PUMP IS LOCATED BELOW THE DESIGN FLOOD ELEVATION. |
| 3. COVERS ON POTABLE WATER WELLS SHALL BE SEALED, |
| EXCEPT WHERE THE TOP OF THE CASING WELL OR PIPE SLEEVE |
| IS ELEVATED TO NOT LESS THAN 1 FOOT (305 MM) ABOVE THE |
| DESIGN FLOOD ELEVATION. |
| 4. SANITARY DRAINAGE PIPING. |
| 5. STORM DRAINAGE PIPING. |
| 6. MANHOLE COVERS SHALL BE SEALED, EXCEPT WHERE |
| ELEVATED TO OR ABOVE THE DESIGN FLOOD ELEVATION. |
| 7. OTHER PLUMBING FIXTURES, FAUCETS, FIXTURE FITTINGS, |
| PIPING SYSTEMS AND EQUIPMENT. |
| 8. WATER HEATERS. |
| 9. VENTS AND VENT SYSTEMS. |
| |
| EXCEPTION: THE SYSTEMS LISTED IN THIS SECTION ARE |
| PERMITTED TO BE LOCATED BELOW THE ELEVATION REQUIRED BY |
| SECTION 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR |
| UTILITIES AND ATTENDANT EQUIPMENT, PROVIDED THAT THE |
| SYSTEMS ARE DESIGNED AND INSTALLED TO PREVENT WATER |
| FROM ENTERING OR ACCUMULATING WITHIN THEIR COMPONENTS |
| AND THE SYSTEMS ARE CONSTRUCTED TO RESIST HYDROSTATIC |
| AND HYDRODYNAMIC LOADS AND STRESSES, INCLUDING THE |
| EFFECTS OF BUOYANCY, DURING THE OCCURRENCE OF FLOODING |
| UP TO SUCH ELEVATION. |
| PLEASE SEE SECTION |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |