2021-06-07 11:55:46 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL25621.01-R1 IS NOT RATED FOR USE IN ZONE 2 & |
| 3 FOR STRUCTURES LOCATED IN EXPOSURE B, C, OR D WITH |
| FLAT ROOF LESS THAN 7 DEGREES, HIP ROOF WITH MAX SLOPE |
| OF 12:12 OR GABLE ROOF WITH SLOPE BETWEEN 4.4:12 & |
| 12:12 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS |
| WIND SPEED 170 MPH. PROVIDE SIGNED AND SEALED |
| ENGINEERING FOR USE OR SELECT A SYSTEM THAT MEETS THE |
| ABOVE CRITERIA. PROJECT LOCATED IN EXPOSURE D CATEGORY |
| AREA. |
| 2. SUBMITTED PRODUCT APPROVAL FL2569-R20 HAS BEEN |
| REVISED TO FL2569-R21. PLEASE PROVIDE A COMPLETE SET. |
| ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| RULE 61G20-3. |
| |