2021-06-21 13:03:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PANEL IN CABANA IS IN A CLOSET. NOT IN VICINITY OF
 EASILY IGNITIBLE MATERIAL. OVERCURRENT DEVICES S HALL
 NOT BE LOCATED IN THE VICINITY OF EASILY IGNITIBLE
 MATERIAL, SUCH AS IN CLOTHES CLOSETS 240.24(D)
  
 PANEL IN CABANA NEEDS A GROUNDING ELECTRODE SYSTEM
 250.32
  
 PANEL "P" NEEDS A MAIN BREAKER PER 225.33 NO MORE THAN
 6 SETS OF BREAKERS IN A PANEL REMOTE FROM BUILDING.
  
 225.33 MAXIMUM NUMBER OF DISCONNECTS (A) GENERAL. TH E
 DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY 225.30
 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR SIX
 CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN A
 GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A SWITCHBOARD
 OR SWITCHGEAR. THERE SHALL BE NO MORE THAN SIX
 DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION