2021-06-15 13:23:03 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21060066 1701 S FLAGLER DR # 503 |
| |
| NOTE: UNIT IS ON THE 5TH FLOOR OF 19 FLOOR CONDOMINIUM. |
| NOTE: PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE |
| SUBMITTED WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND |
| LICENSE NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A |
| PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| ISSUANCE OF A PERMIT. |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1.AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, A SEPARATE PLUMBING |
| PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR |
| THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| LICENSED IN THE PLUMBING TRADE. ADDITIONALLY, THE |
| SHOWER PAN DETAIL SHALL BEAR THE PRINTED NAME, THE |
| SIGNATURE AND THE CERTIFICATION NUMBER OF THE DESIGNER |
| WHO SHALL BE A CONTRACTOR LICENSED IN THE PLUMBING |
| TRADE. |
| |
| 2.PER WPB FBC 104.1, A PLUMBING SUB-PERMIT APPLICATION |
| SHALL BE SUBMITTED FOR THIS PROJECT BY A LICENSED |
| PLUMBING CONTRACTOR. |
| |
| 3.SCOPE OF WORK INCLUDES REPLACEMENT OF EXISTING WATER |
| HEATER WITH LIKE FOR LIKE. PER WPB FBC 107.2.1, PROVIDE |
| THE FOLLOWING: |
| A) LOCATION OF WATER HEATER |
| B) DESCRIPTION (MANUFACTURER, MODEL #, CAPACITY (GPM |
| FOR TANKLESS), ELECTRICAL OR GAS CHARACTERISTICS) OF |
| THE EXISTING WATER HEATER. |
| C) NEW WATER HEATER SCHEDULE; MANUFACTURER, MODEL #, |
| CAPACITY (GPM FOR TANKLESS), ELECTRICAL OR GAS |
| CHARACTERISTICS. |
| D) WATER HEATER DETAIL- PROVIDE DETAIL OF WATER HEATER |
| SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, |
| HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE |
| FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE |
| (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION) |
| AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) |
| PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1, |
| 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND |
| 504.7.2. IT IS NOTED THAT PER FBC PL 504.7.2 A PAN IS |
| NOT REQUIRED FOR A REPLACEMENT WATER HEATER IF A PAN |
| WAS NOT PREVIOUSLY INSTALLED. |
| |
| 4.PER WPB FBC 107.2.1, PROVIDE A RISER DIAGRAM AND PLAN |
| VIEW SHOWING HOW THE TUB DRAIN IS TO BE CONVERTED TO A |
| VENTED LAVATORY DRAIN. PLEASE NOTE THAT AIR ADMITTANCE |
| VALVES INSTALLED MORE THAN FOUR BRANCH INTERVALS BELOW |
| THE TOP OF THE STACK ARE SUBJECT TO STRINGENT |
| RESTRICTIONS AS NOTED IN FBC PL 918.3.1. |
| |
| 5.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| ACCORDANCE WITH FBC PL TABLE 308.5.", FOR ANY NEW |
| PIPING. |
| |
| 6.PER WPB FBC 107.2.1, PROVIDE FIRE RATED FLOOR |
| DETAIL(S) FOR NEW FLOOR PENETRATIONS AND FOR THE |
| SAFEING OF THE ABANDONED TUB BOX. COMPLY WITH FBC |
| CHAPTER 7. PER FBC PL 315.1, ANNULAR SPACES CREATED BY |
| PIPES PENETRATING FIRE-RESISTANCE-RATED ASSEMBLIES OR |
| MEMBRANES OF SUCH ASSEMBLIES SHALL BE SEALED OR CLOSED |
| IN ACCORDANCE WITH SECTION 714 OF THE FLORIDA BUILDING |
| CODE, BUILDING. |
| |
| 7.PER WPB FBC 107.2.1, PROVIDE DIMENSIONS IN BATHROOMS |
| (INCLUDE NEW SHOWER DIMENSIONS). PROVIDE CENTERLINE |
| DIMENSION FROM WATER CLOSET TO ADJACENT SHOWER |
| ENCLOSURE. PER FBC PL 406.3.1, A WATER CLOSET, URINAL, |
| LAVATORY OR BIDET SHALL NOT BE SET CLOSER THAN 15 |
| INCHES (381 MM) FROM ITS CENTER TO ANY SIDE WALL, |
| PARTITION, VANITY OR OTHER OBSTRUCTION.405.3.1 |
| |
| 8.THE PLANS ARE UNCLEAR AS TO WHAT IS TO BE DONE WITH |
| THE BATHROOM WALLS AT THE SHOWERS. PER FBC PL 421.4.1, |
| BATHTUB FLOORS, SHOWER FLOORS, WALL AREAS ABOVE |
| BUILT-IN TUBS THAT HAVE INSTALLED SHOWER HEADS AND |
| WALLS IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED OF |
| SMOOTH, CORROSION-RESISTANT AND NONABSORBENT WATERPROOF |
| MATERIALS. WALL MATERIALS SHALL EXTEND TO A HEIGHT OF |
| NOT LESS THAN 6 FEET (1829 MM) ABOVE THE ROOM FLOOR |
| LEVEL, AND NOT LESS THAN 70 INCHES (1778 MM) ABOVE THE |
| DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A |
| WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE |
| TUB OR SHOWER FLOOR. PER WPB FBC 107.2.1, CLARIFY. |
| |
| 9.THE PLANS ARE UNCLEAR AS TO WHAT IS TO BE DONE WITH |
| THE MASTER BATH SHOWER. IS THE FLOOR TILE IN THE SHOWER |
| TO BE REPLACED? IF SO, A TEST AND INSPECTION OF THE |
| SHOWER PAN INSTALLATION IS REQUIRED AND THE PAN SHALL |
| COMPLY WITH THE PROVISIONS OF FBC PL 421.5.2. PER WPB |
| FBC 107.2.1, CLARIFY ON THE PLANS. |
| |
| 10.THE ELECTRICAL PLAN SEEMS TO BE REPRESENTATIVE OF |
| EXISTING CONDITIONS. IF SO, THE WATER CLOSET APPEARS TO |
| BE RELOCATED FROM ITS' ORIGINAL LOCATION. PER WPB FBC |
| 107.2.1, CLARIFY. PROVIDE DRAWINGS SHOWING MODIFICATION |
| IF APPLICABLE.. |
| |
| 11.WATER HAMMER ARRESTORS ARE REQUIRED AT WATER |
| SUPPLIES TO DISHWASHER AND ICE LINE PER FPC PL 604.9. |
| |
| 12.PER FBC PL 409.4, THE WASTE CONNECTION OF A |
| RESIDENTIAL DISHWASHER SHALL CONNECT DIRECTLY TO A WYE |
| BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK, |
| DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD WASTE |
| DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. THE |
| WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE AND |
| BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK RIM |
| OR COUNTER TOP. |
| |
| 13.A ROUGH IN PLUMBING INSPECTION IS REQUIRED FOR |
| SHOWER VALVE REPLACEMENT. NEW SHOWER CONTROL VALVES TO |
| COMPLY WITH FBC PL 412.3, WHICH SHALL BE PRESSURE |
| BALANCED PB, THERMOSTATIC MIXING (TM) OR COMBINATION |
| PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP |
| THAT CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| SHALL BE INSTALLED AT THE POINT OF USE. |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| FROM THE PRIOR REVIEW. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 21060066 1701 S FLAGLER DR # 503 |