Plan Review Notes For Permit 21051655 |
Permit Number |
21051655 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-03-02 11:55:17 | CONCRETE FOUNDATION, STAIR HAND AND GUARD RAILS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) HANDRAIL EXTENSIONS AT THE BOTTOM OF THE STAIR | | SHOULD "CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD | | BEYOND THE BOTTOM RISER" - PLEASE SHOW HAND RAIL | | EXTENSIONS 1014.6 HANDRAIL EXTENSIONS. | | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING | | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN | | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL | | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) | | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE | | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. | | | | 2) DRAWINGS NEED TO SHOW THE ATTACHMENTS (TYPE, SIZE, | | AMOUNT) OF THE HANDRAILS AND GUARDRAILS TO THE EXISTING | | STRUCTURE FBC WPB 107.2 | | | | 3) HANDRAIL SHOP DRAWINGS NEED TO BE REVIEWED AND | | MARKED APPROVED BY THE DESIGNER OF RECORD (JOSEPH J. | | FRANKO) FBC WPB 107.3.4 |
|