Plan Review Notes For Permit 21051655 |
Permit Number |
21051655 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-02-14 10:56:50 | CONCRETE FOUNDATION, STAIR HAND AND GUARD RAILS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | 2ND REVIEW | | | | CORRECTIONS NEEDED - | | 1) PLEASE PROVIDE HAND AND GUARD RAIL DETAILS SIGNED BY | | THE DESIGN PROFESSIONAL SHOWING ALL ATTACHMENT TO THE | | EXISTING STAIR TO COMPLY WITH FBC 1014 AND 1607.8 | | 2) PLEASE SHOW OPENINGS IN THE GUARD RAILS TO COMPLY | | WITH FBC 1015.4 | | 3) PLEASE SHOW THE HEIGHT OF HAND AND GUARD RAILS TO | | COMPLY WITH FBC 1015.3 AND 1014.2 | | 4) PLEASE SHOW HAND RAIL EXTENSIONS 1014.6 HANDRAIL | | EXTENSIONS. | | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING | | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN | | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL | | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) | | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE | | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
|