2021-06-04 14:45:071ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21051630
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS REQUIRE
 VARIABLE AIR VOLUME DEVICES FOR THIS PROJECT. PLEASE
 SHOW THESE ON THE DRAWING.
  
 2) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 NAMES OF EACH SPACE IN THE BUILDING. FBC 107.2.1
  
 3) IT APPEARS FROM THE DRAWING THAT THE CONDENSING
 UNITS ARE LOCATED IN THE PARKING LOT, PLEASE SHOW HOW
 YOU WILL PROVIDE PROTECTION FROM DAMAGE FOR THESE
 UNITS. FBC M 303.4
  
 4) PLEASE SHOW THE CONDENSATION PIPING MATERIAL AND THE
 TERMINATION LOCATION. FBC M 307
  
 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED OFF OF
 THE 2020 FBC M 403.3.1.1 AND TABLE 403.3.1.1 FOR EACH
 SPACE OF THE TENANT SPACE.
  
 6) THE DESIGNER OF THE DRAWING MUST INCLUDE THE ADDRESS
 THE WORK IS BEING INSTALLED, THEIR NAME AND THEIR
 SIGNATURE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  