Plan Review Notes
Plan Review Notes For Permit 21051622
Permit Number 21051622
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-30 13:53:4106/30/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW ON THE POOL PUMP CURVE. THIS IS NEEDED
 TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1. INDICATE ON THE PUMP CURVE WHICH CURVE
 KEY IS FOR THE PUMP BEING INSTALLED ON THIS SYSTEM PER
 THE WPB AMEND. TO FBC SEC. 107.2.1.
  
 2. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE PUMP, HEAT PUMP, FILTER AND CHLORINATOR IF USED PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. ON-PAGE 3-3, THE EQUIPMENT LAYOUT HAS THREE F'S AND
 THERE IS NO G OR H. PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF
 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2,
 STANDARD RATING CONDITIONS ? LOW AIR TEMPERATURE. A
 TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED
 TO VERIFY PROCEDURE COMPLIANCE PER THE 2020 FBC-ENERGY
 SEC. R 403.10.5. PLEASE PROVIDE DOCUMENTATION.
  
 5. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE
 WILL BE REQUIRED AT THE WATER METER BY A LICENSED
 CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE
 CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE
 CROSS CONNECTION CONTROL MANUAL PAGE 11 (C). THIS IS
 DUE TO THE AUTOFILL ON THE POOL, WHICH WILL REQUIRE A
 BACKFLOW DEVICE (P.V.B. ISOLATION), AND IT WILL BE
 REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW
 CONTRACTOR. A REPORT MUST BE FILLED OUT FOR THE P.V.B.
 AND WILL NEED TO BE WITH THE PERMIT AT THE FINAL. THE
 INSPECTOR WILL TAKE THE CERTIFICATION FOR CITY RECORDS.
 THESE TWO BACKFLOWS CAN BE COMBINED IN THE SAME PERMIT.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved