2021-06-16 11:56:20 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21051556 |
| 6/16/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| A COMPREHENSIVE AND THOROUGH REVIEW OF THE INDOOR |
| GREASE INTERCEPTOR CANNOT BE COMPLETED AT THIS TIME DUE |
| TO A LACK OF REQUIRED COMPLIANCE INFORMATION ( SEE |
| COMMENTS 1 & 2 LISTED BELOW), AND ALSO DUE TO THE FACT |
| THAT NO PERMIT FOR THE TENANT SPACE BUILDOUT HAS BEEN |
| ISSUE OR EVEN APPLIED FOR. GREASE INTERCEPTOR PERMITS |
| ARE TYPICALLY ISSUED IN CONJUNCTION WITH PERMITS ISSUED |
| FOR RESTAURANT AND OTHER OCCUPANCIES WHERE GREASE LADEN |
| WASTE IS PRODUCED AS A BY-PRODUCT OF COOKING AND |
| CLEANING OPERATIONS. CURRENTLY THERE IS NO PERMIT |
| APPLICATION AND PLAN SUBMITTED FOR THE PROPOSED |
| OCCUPANCY. |
| |
| 1) PROVIDE A DIMENSIONED AND DETAILED PLAN SHOWING THE |
| LOCATION OF THE INTERCEPTOR AND PLUMBING PIPING |
| REQUIREMENTS. SHOW THE GREASE WASTE PIPING RUNS FROM |
| THE FIXTURES TO THE INTERCEPTOR AND FROM THE |
| INTERCEPTOR TO POINT OF CONNECTION TO THE EXISTING |
| BUILDING OR SEWER DRAIN. SHOW LOCATIONS OF ALL REQUIRED |
| CLEANOUTS AND VENTS PER MANUFACTURER?S SPECIFICATIONS- |
| SECTION 1003.3.5 FBC P AND SECTION 107.2.1 WPB. |
| |
| 2) PROVIDE GREASE WASTE CALCULATIONS AND INTERCEPTOR |
| EQUIPMENT SCHEDULE ON THE PLAN IN COMPLIANCE WITH |
| SECTION 1003.3.5 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |