2021-06-16 10:41:13 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21051535 |
| 6/16/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER: WPB BUILDING DEPT. RECORDS SHOW GAS |
| PERMIT- 94015183- 10842 EGRET POINTE LN. FOR A 335,000 |
| BTU POOL HEATER AND A 40,000 BTU GRILL (TOTAL LOAD- |
| 375,000 BTU). THE RISER SHOWS AN EXISTING 440,000 BTU |
| LOAD. YOU ARE UPGRADING TO A 2-PSI SYSTEM. PLEASE SHOW |
| THE BRANCH PIPE RUNS TO THE EXISTING APPLIANCES AND |
| PROVIDE EITHER NEW STEP-DOWN REGULATORS FOR EACH |
| APPLIANCE, OR VERIFY THE EXISTING REGULATORS CAN HANDLE |
| INPUT PRESSURES OF 2 PSI- SECTIONS G2412.3, G2412.4 & |
| G2421.2 FBC RES. |
| |
| 2) CORRECT THE SURVEY INDICATING THE GENERATOR EXHAUST |
| TO BE 5 FT. FROM ANY OPENING- MINIMUM 10 FT. CLEARANCE |
| IS REQUIRED- SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |